9.6.2
Connectable cable cross-sections
Table 9-7
Connectable cable cross-sections: Power supply cable / motor cable, part 1
Component
Motor Module
3 A to 30 A
2 x 3 A to 2 x 18 A
Motor Module
45 A to 60 A
Motor Module 85 A
Motor Module
132 A to 200 A
Smart Line Module
5 kW to 10 kW
Acitve Line Module 16 kW
Smart Line Module 16 kW
Acitve Line Module 36 kW
Smart Line Module 36 kW
Acitve Line Module 55 kW
Active Line Module
80 kW to 120 kW
1) for ring cable lugs to DIN 46234
Terminal area for flexible cable with wire end ferrule
Terminal area for flexible cable with ring cable lug M6
Terminal area for flexible cable with ring cable lug M8
IP2xB to EN 60529 ensured; note: the shock-hazard protection installed as standard must be used or adjusted as appropriate.
AC Drive
Manual, (GH6), 07/2007 Edition, 6SL3097-2AL00-0BP2
Cabinet Design and EMC for Components, Blocksize Format
Terminal type
Motor connector 30 A 3+2 pin
Threaded bolt M6/6 Nm
1)
Threaded bolt M8 / 13 Nm
Threaded bolt M8 / 13 Nm
Screw-type terminal
Screw-type terminal
Threaded bolt M6 / 6 Nm
Threaded bolt M8 / 13 Nm
Threaded bolt M8 / 13 Nm
Connection cross-section [mm
1.5
2.5
4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
9.6 Connection methods
]
2
6
10
16
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
307