Description Of The Leds On The Cua32 Control Unit Adapter - Siemens SINAMICS S120 Manual

Sinamics family modular motion control drives
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Control Units
6.5 CUA32 Control Unit Adapter
6.5.3.6

Description of the LEDs on the CUA32 Control Unit Adapter

Table 6-44
Description of the LEDs on the CUA32 Control Unit Adapter
LED
Color
RDY
Red
(READY)
Green
-
OUT > 5V
Orange
Cause and rectification of faults
The following reference contains information about the cause and rectification of faults:
Reference: /IH1/ SINAMICS S120 Commissioning Manual.
226
Status
Description
Continuous
At least one fault is present in this component.
Continuous
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Off
Electronics power supply is missing or outside permissible tolerance
range.
Power supply ≤5 V.
Electronics power supply for measuring system available.
Power supply >5 V.
Caution
Continuous
You must ensure that the connected encoder can be operated with a
24 V power supply.
If an encoder that is designed for a 5 V power supply is operated with
a 24 V power supply, this can destroy the encoder electronics.
Manual, (GH6), 07/2007 Edition, 6SL3097-2AL00-0BP2
AC Drive