Siemens SINAMICS S120 Manual page 95

Sinamics family modular motion control drives
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 3-13
Technical data PM340, Part 5
Line voltage 3-ph. 380 V to 480 V AC
PM340
PM340 with integrated line
filter
Rated output current I
n
Base load current I
H
Output current for S6 duty
(40%) l
S6
Max. output current I
max
Rated power based on I
n
Rated power based on I
H
Rated pulse frequency
Power loss
Cooling air requirement
Sound pressure level
24 V DC supply for the
Control Unit
Rated input current
1)
with line reactor
-
- without line reactor
Resistance value of the
external braking resistor
Max. cable length to braking
resistor
Line supply connection
L, N
Motor connection
U2, V2, W2
DC link connection,
connection for braking
resistor DCP/R1, DCN, R2
PE connection
Max. motor cable length
2)
Degree of protection
Height
PM 340 with integrated line
filter
Depth
- PM340 with Control Unit
CU310
- PM340 with CUA31
Frame size
AC Drive
Manual, (GH6), 07/2007 Edition, 6SL3097-2AL00-0BP2
6SL3210-
1SE31-0UA0
6SL3210-
1SE31-0AA0
A
90
A
80
A
117
A
150
kW
45
kW
37
kHz
4
kW
1.21
m
/s
0.039
3
dB(A)
62
A
1.0
A
94
105
Ohms
> 15
m
15
Stud M6,
connectable cable
cross-sections 10 to
35 mm
2
Stud M6,
connectable cable
cross-sections 10 to
35 mm
2
Stud M6,
connectable cable
cross-sections 10 to
35 mm
2
at the housing with
M6 screw
m
70 (shielded)
100 (unshielded)
IP20 or IPXXB
mm
633 (24.92)
mm
293.1 (11.53)
233.8 (9.20)
FSE
3.1 Power Modules Blocksize (PM340)
1SE31-1UA0
1SE31-5UA0
1SE31-1AA0
1SE31-5AA0
110
145
95
115
143
188
180
220
55
75
45
55
4
4
1.42
1.93
0.094
0.094
< 60
< 60
1.0
1.0
115
151
129
168
> 8.2
> 8.2
15
15
Stud M8,
Stud M8,
max. connectable
max. connectable
cable cross-section
cable cross-section
120 mm
120 mm
2
Stud M8,
Stud M8,
max. connectable
max. connectable
cable cross-section
cable cross-section
120 mm
120 mm
2
Stud M8,
Stud M8,
max. connectable
max. connectable
cable cross-section
cable cross-section
120 mm
120 mm
2
At the housing with
At the housing with
M8 screw
M8 screw
70 (shielded)
70 (shielded)
100 (unshielded)
100 (unshielded)
IP20 or IPXXB
IP20 or IPXXB
934 (36.77)
934 (36.77)
405.1 (15.94)
405.1 (15.94)
345.8 (13.61)
345.8 (13.61)
FSF
FSF
Power Modules
1SE31-8UA0
1SE31-8AA0
178
155
231
290
90
75
4
2.31
0.117
65
1.0
186
204
> 8.2
15
Stud M8,
max. connectable
cable cross-section
120 mm
2
2
Stud M8,
max. connectable
cable cross-section
120 mm
2
2
Stud M8,
max. connectable
cable cross-section
120 mm
2
2
At the housing with
M8 screw
70 (shielded)
100 (unshielded)
IP20 or IPXXB
934 (36.77)
405.1 (15.94)
345.8 (13.61)
FSF
95

Hide quick links:

Advertisement

Table of Contents
loading