Power Modules
3.2 Power Modules Chassis
High overload
The base load current for high overload IH is based on a load duty cycle of 150% for 60 s or
160% for 10 s with a load duty duration of 300 s.
Figure 3-38
3.2.7.2

Current de-rating as a function of the pulse frequency

When the pulse frequency is increased, the derating factor of the output current must be
taken into account.
This derating factor must be applied to the currents specified in the technical data.
Table 3-23
Derating factor of the output current as a function of the pulse frequency
Order No.
6SL3310-...
for a pulse frequency of
1TE32-1AA0
1TE32-6AA0
1TE33-1AA0
1TE33-8AA0
1TE35-0AA0
116
High overload
Output current
Permissible output
for a pulse frequency of
2 kHz [A]
210
260
310
380
490
Derating factor
current
for a pulse frequency of
2.5 kHz
as a % of In
95 %
95 %
97 %
96 %
94 %
Manual, (GH6), 07/2007 Edition, 6SL3097-2AL00-0BP2
Derating factor
for a pulse frequency of
4 kHz
82 %
83 %
88 %
87 %
78 %
8 kHz
50 %
50 %
50 %
50 %
50 %