Technical Data, Chassis - Siemens SINAMICS S120 Manual

Sinamics family modular motion control drives
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-Side Power Components
2.4 Line reactors
2.4.8

Technical data, Chassis

Table 2-16
Technical data, Chassis line reactors
Order No.
Suitable for
Power Module
Rated current of the
Power Module
Rated voltage
Rated line reactor current
I
thmax
Power loss 50/60 Hz
Line supply/load
connection
Degree of protection
Weight
60
6SL3000-
0CE32-3AA0
6SL3310-
1TE32-1AA0
A
210
V
3-ph. 380 V AC -10% to 3-ph. 480 V AC +10% (-15% < 1 min), 47 to 63 Hz
A
210
A
224
kW
0.243/0.274
Connection
lugs M10
IP00
kg
24.5
0CE32-8AA0
0CE33-3AA0
1TE32-6AA0
1TE33-1AA0
260
310
260
310
278
331
0.219/0.247
0.236/0.267
Connection
Connection
lugs M10
lugs M10
IP00
IP00
26
27.8
Manual, (GH6), 07/2007 Edition, 6SL3097-2AL00-0BP2
0CE35-1AA0
0CE35-1AA0
1TE33-8AA0
1TE35-0AA0
380
380
380
380
508
508
0.323/0.365
0.323/0.365
Connection
Connection
lugs M12
lugs M12
IP00
IP00
38
38
AC Drive