used function. In the next items a detailed description of each of these objects is presented, where the inverter
parameters used to execute these object functions are indicated.
Device Control
6.1
Every drive operating in a CANopen network following the DSP 402 must be in accordance with the description of
the following state machine:
Estate descriptions:
Not ready to switch on
Switch on disabled
Ready to switch on: Command to allow powering up the drive has been received.
Switched on
: Command for powering up the drive has been received.
Operation enabled
Power is being applied to the motor.
Quick stop active
the motor.
Fault reaction active
Fault
: Drive with fault. Disabled function, without power being applied to the motor.
NOTE!
The frequency inverter CFW-11 does not have a switch for disabling / enabling the power section
supply of the equipment. Therefore, the states described in the
implemented for a matter of compatibility with the described state machine; however the power section
supply remains active even in these states.
Description of the transitions:
Transition 0: The drive is switched on and the initialization procedure starts. The power section supply of the
drive is active.
Transition 1: Initialization completed (automatic).
– Objects for Controlling the Drive
Figure 6.2 - State machine for drives
: The inverter is initializing, it cannot be commanded.
: Initialization complete, the inverter is able to receive commands.
: The drive is enabled, being controlled according to the programmed operation mode.
: During the operation, the
: A fault has occurred and the drive is performing the action related to the type of fault.
quick stop
command was received. Power is being applied to
Power disabled
group were