P0700 - Can Protocol; P0701 - Can Address; P0702 - Can Baud Rate - WEG CFW-11 Communications Manual

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

NOTE!
If the analog output is programmed for working from -10V to +10V, negative values must be
programmed at the specific parameter, so that -32769 to 32767 represent a variation from -10V to
+10V at the output.
P0700 – CAN Protocol
Range:
1 = CANopen
2 = DeviceNet
Proprieties: CFG, CAN
Access groups via HMI:
01 PARAMETER GROUPS.
∟ 49 Communication
∟ 112 CANopen/DeviceNet
Description:
It allows selecting the desired protocol for the CAN interface. In order to enable the CANopen protocol, it is
necessary to program this parameter with the option '1 = CANopen'.
If this parameter is changed, it becomes valid only after cycling power of the inverter.
P0701 – CAN Address
Range:
0 to 127
Proprieties:
CFG, CAN
Access groups via HMI:
01 PARAMETER GROUPS.
∟ 49 Communication
∟ 112 CANopen/DeviceNet
Description:
It allows programming the inverter address used for the CAN communication. It is necessary that each element of
the network has an address different from the others. The valid addresses for this parameter depend on the protocol
programmed in P0700:
P0700 = 1 (CANopen) → valid addresses: 1 to 127.
P0700 = 2 (DeviceNet) → valid addresses: 0 to 63.
If this parameter is changed, it becomes valid only after cycling power of the inverter.
P0702 – CAN Baud Rate
Range:
0 = 1 Mbit/s
1 = 800 Kbit/s
2 = 500 Kbit/s
3 = 250 Kbit/s
4 = 125 Kbit/s
5 = 100 Kbit/s
6 = 50 Kbit/s
7 = 20 Kbit/s
8 = 10 Kbit/s
Proprieties:
CFG, CAN
Access groups via HMI:
01 PARAMETER
GROUPS.
∟ 49 Communication
∟ 112 CANopen/DeviceNet
.
.
.
Default:
2
Default:
63
Default:
0