Optional Components; Rack Compatibility - Oracle SPARC S7-2 Installation Manual

Compact cloud server
Hide thumbs Also See for SPARC S7-2:
Table of Contents

Advertisement

Optional Components

Optional Components
Optional components, such as additional memory or PCIe cards that were ordered as part of the
system, are installed in the server at the factory before the server is shipped. Any options not
ordered with the system are shipped separately. If possible, install these components prior to
installing the server in a rack.
Except for the rackmount kits, if you ordered any options that are not factory-installed, refer
to the service manual for the server and the component's documentation for installation
instructions.
Related Information
Optional component documentation
Server Service

Rack Compatibility

Check that your rack is compatible with the slide rail and cable management assembly options.
The optional slide rails are compatible with a wide range of equipment racks that meet the
following standards.
Item
Structure
Rack horizontal opening and unit vertical pitch
Distance between front and rear mounting
planes
Clearance depth in front of front mounting
plane
Clearance depth behind front mounting plane
Clearance width between front and rear
mounting planes
26
SPARC S7-2 Server Installation Guide • July 2016
Requirement
Four-post rack (mounting at both front and rear). Supported rack
types: square hole (9.5 mm) and round hole (M6 or 1/4-20 threaded
only.
Two-post racks are not compatible.
Conforms to ANSI/EIA 310-D-1992 or IEC 60927 standards.
Minimum 61 cm and maximum 91.5 cm (24 inches to 36 inches).
Distance to front cabinet door is at least 2.54 cm (1 inch).
Distance to rear cabinet door is at least 90 cm (35.43 inches) with
the cable management arm, or 80 cm (31.5 inches) without the
cable management arm.
Distance between structural supports and cable troughs is at least
45.6 cm (18 inches).