Start-up and Program Tests

4.1

Operating Instructions

4.1.1

CPU Operator Panel

Battery low
(yellow LED lights:
battery discharged or
not installed)
ON/OFF switch
ON/OFF Switch
The ON/OFF switch turns on the CPU's voltage regulators. This switch does NOT separate the
voltage regulator from the L+/M terminals.
Operating Mode Switch
Use the operating mode switch to select either the RUN or STOP operating mode. The CPU
automatically goes into the START-UP mode during the transition from STOP to RUN (see section
7.4.2).

4.1.2 Operating Modes

STOP Operating Mode
The program is not executed.
The current values for timers, counters, flags, and process image I/O tables are saved when the
STOP mode begins.
The output modules are disabled (signal status "0").
The process image I/O tables, timers, and non-retentive flags and counters are set to "zero"
during the transition from STOP to RUN.
RUN Operating Mode
The program is processed cyclically.
Already started timers continue to run.
The signal states for the input modules are stored.
The output modules are addressed.
The RUN operating mode can also be set after an OVERALL RESET, that is, when the program
memory is empty.
EWA 4NEB 812 6120-02
BATTERY
OFF/
LOW
RUN
I
STOP
O
COPY
Figure 4.1 CPU Operator Panel

Start-up and Program Tests

Operating mode display
RUN
(green LED: RUN)
Operating mode display
STOP
(red LED: STOP)
Operating mode switch
4-1