S5-100U
Analog Output Module 2×± 20 mA
1
2
4
6
8
10
R 300
ANALOG OUTPUT
2 x± 20 mA
6ES5 470-8MB12
1 2
3
4
0V
- 15V
+15V
1
3
5
2
4
+QI
M ANA
L+
M
Ch.0
Legend:
QI: Analog output "current"
EWA 4NEB 812 6120-02a
L+
+
M
24 V
QI
R
Ch.0
M ANA
QI
R
Ch.1
M ANA
6
5
6
+9 V
GND
Data
7
9
6
8
10
+QI
M ANA
Ch.1
Technical specifications
Address designation
(for ET 100U only)
Output range
(rated values)
Number of outputs
Galvanic isolation
Input resistance
max.
Connection method
Digital representation
of output signal
Measured value
representation
Conversion time
(0 to 100%)
max.
Permissible overload
Short-circuit protection
Short-circuit current
Permissible voltage
difference to central
ground point and
between outputs
max.
Basic error limits
Operating error limits
(0 to 60 °C)
(32 to 140 °F)
Single errors
- linearity
- polarity reversal error
- temperature error
Length of cable
- shielded
max.
Supply voltage L+
- rated value
- ripple V
PP
- permissible range
(ripple included)
Insulation rating
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Rated insulation voltage
(output to L+, between
outputs, output to + 9 V)
- insulation group
- tested with
Current consumption
- from + 9 V (CPU)
typ.
- from L +
typ.
Power loss of the
module
typ.
Weight
approx.
Module Spectrum
(6ES5 470-8MB12)
2 AQ
±20 mA
2
yes (outputs to
grounding point and
between outputs)
300
two-wire connection
11 bits + sign
(1024 units =rated
value)
two's complement
(left-justified)
0.15 ms
25%
yes
± 30 mA
75 V DC/60 V AC
±0.3%
±0.6%
±0.2%
±0.1%
±0.01%/K
200 m (660 ft.)
24 V DC
3.6 V
20 to 30 V
VDE 0160
12 V AC
1 x B
500 V AC
60 V AC
1 x B
500 V AC
170 mA
130 mA
3.8 W
290 g (10 oz.)