Siemens S5-100U User Manual page 437

Simatic s5 programmable controller
Hide thumbs Also See for S5-100U:
Table of Contents

Advertisement

S5-100U
Example 2:
Approaching a Setpoint in Down-Count Direction
Enable input
Output,
diagnostic bit
setpoint reached
Example of
1000
actual value
Figure 15-23. Approaching a Setpoint in Down-Count Direction
Actual value= 7000: The enable input is set to "1".
Actual value= 3000: The setpoint is reached, the output and the diagnostic bit "setpoint
reached" are set.
Actual value= 1000: The enable input is set to "0", the output and the diagnostic bit are reset.
Example 3:
Reversal of Direction after Approaching a Setpoint
Enable input
Output,
diagnostic bit
setpoint reached
Example of
1000
actual value
Figure 15-24. Approaching a Setpoint in Up-Count Direction and
Actual value=1000: The enable input is set to "1".
Actual value=3000: The setpoint is reached, the output and the diagnostic bit "setpoint
reached" are set.
Actual value=4500: The traversing path is reversed.
Actual value=1000: The enable input is set to "0", the output and the diagnostic bit are reset.
Note
Set outputs can be reset only via a "0" signal to the enable input.
15-36
Direction of traverse
Setpoint
2000
3000
Direction of traverse
Setpoint
Direction of traverse
2000
3000
Consecutive Reversal of Direction
4000
5000
6000
Change of direction
4000
5000
6000
Function Modules
7000
7000
EWA 4NEB 812 6120-02

Advertisement

Table of Contents
loading

Table of Contents