Analog Value Processing
STL
JU FB 250
NAME
: RLG:AI
BG
: 0
KNKT
: 0.3
OGR
: 300
UGR
: 0
EINZ
:
XA
: FW1
FB
:F0.0
BU
:F0.1
JU FB 241
. . .
The BCD number is stored in flag bytes 11 to 13. Output is via two 8-channel digital output
modules in slots 2 and 3. The BCD tetrads 5 and 6 stored in flag word 11 need not be output
since the number has only three digits.
STL
. . .
L FW12
T QW2
BE
11-24
Explanation
Unconditional call FB250
Slot 0
Channel 0, channel type 3
Upper limit: 30.0 m
Lower limit: 0.0 m
No meaning
Make-up quantity stored in flag word 1 as fixed-point number
"1", if wire break
"1", if tank too full
Conversion of fixed-point number into
BCD number
Read tetrads 0 to 3 of the BCD number
and transfer to output modules.
3
3
Explanation
S5-100U
EWA 4NEB 812 6120-02