Siemens S5-100U User Manual page 280

Simatic s5 programmable controller
Hide thumbs Also See for S5-100U:
Table of Contents

Advertisement

S5-100U
Table 11-10. Analog Input Module 464-8MA21, 4x±50 mV "with Linearization"
and "with Temperature Compensation" (Bipolar); Thermoelement Type K
(Nickel-Chromium/Nickel-Aluminium, according to IEC 584)
Thermal
Units
Voltage
in mV*
>2359
1370
1369
54.773
1000
41.269
500
20.640
150
6.137
100
4.095
1
0.039
0
0
-1
-0.039
-100
-3.553
-101
-3.584
-150
-4.912
-200
-5.891
-201
-273
X
*
For a reference temperature of 0° C (32° F)
**
In the overrange area, the current slope of the characteristic curve is maintained when leaving
the linearized nominal range.
11-14
Temperature
° C
° F
0 1 0 0 1 0 0 1 1 0 1 1 1 0 0 1 Overflow
1370
2498
0 0 1 0 1 0 1 0 1 1 0 1 0 0 0 1
1369
2496
0 0 1 0 1 0 1 0 1 1 0 0 1 0 0 0
1000
1832
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0
500
932
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
150
302
0 0 0 0 0 1 0 0 1 0 1 1 0 0 0 0
100
212
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0 Nominal range
1
34
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
32
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1
-30
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
-100
-148
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
-101
-150
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 Accuracy
-150
-238
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0 0
-200
-328
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 0
-201
-330
1 1 1 1 1 0 0 1 1 0 1 1 1 0 0 1 Overrange
1 1 1 1 0 0 0 0 1 0 0 1 0 0 0 1 Overflow
X
X X X X X X X X X X X X X 0 1 0 Wire break
This value corresponds to the terminal temperature at wire break
High Byte
Analog Value Processing
Low Byte
Range
Overrange
2 K
EWA 4NEB 812 6120-02
**
**