15.6.6 Addressing

The counter module is addressed like an analog module (see section 6.3).
The module may only be plugged into slots 0 to 7.
The address range extends from byte 64 to byte 127.
In both process image tables, eight bytes are reserved per slot and of these eight bytes only the
first four are used.
Slot Addressing
Slot
0
64
Address
to
PII/PIQ
71
Meaning of the Bytes of a Slot Address (Example: Slot 1)
Table 15-7. Meaning of the Address Bytes of a Slot Address (Example: Slot 1)
Byte
Byte
Number
Address
0
72
1
73
2
74
3
75
4 to 7
76 to 79
EWA 4NEB 812 6120-02
Table 15-6. Slot Addressing
1
2
72
80
to
to
79
87
Meaning in PII
Irrelevant
Diagnostic byte
High
byte
Low
byte
3
4
88
96
104
to
to
95
103
111
High
byte
Low
byte
High
byte
Actual value
Low
byte
Irrelevant
S5100U
5
6
112
120
to
to
119
127
Meaning in PIQ
Setpoint 1
Setpoint 2
7
to
15-39