Positioning Module Ip 266 - Siemens S5-100U User Manual

Simatic s5 programmable controller
Hide thumbs Also See for S5-100U:
Table of Contents

Advertisement

Function Modules
15.8

Positioning Module IP 266

FAULT
ANALOG
OUT
E
N
C
O
D
E
R
POSITIONING CONT.
MODULE IP 266
6ES5 266-8MA11
1 2
3
4
5
EWA 4NEB 812 6120-02
P
G
6
6
Technical Specifications
Address designation
(only for ET 200)
Analog Output
Output signal range
Digital signal representation
Short-circuit proof
Reference potential of the
analog output signal
Cable length shielded
max.
Pulse Input
Position decoder
Traverse range
Input voltages for the tracks
- differential inputs
- asymmetrical inputs
Supply voltage for
the sensor
(short-circuit proof)
Input Frequency and
Cable Length
Symmetrical sensors (5 V) max.
max.
Asymmetrical sensors
(24 V)
max.
max.
Input Signals
Digital Inputs
Input voltage range
Galvanic isolation
"0" signal
"1" signal
Permissible zero signal
current at "0" signal
Typ. input current at 24 V
Digital Outputs
Output voltage range
Galvanic isolation
Max. output current at
"1" signal
Short-circuit protector
Cable length shielded
max.
Supply Voltage
Logic voltage from 24-V
ext. supply produced
with switched-mode
power supply
Current consumption from
24-V supply without out-
puts and 24-V sensor
typ.
S5-100U
(6ES5 266-8MA11)
095
±10 V
13 bits plus sign
yes
analog ground of the
power section
32 m (105 ft.)
incremental
±32767.999 mm/
0.1 inch/degree
5 V/RS 422
24 V/typ. 7.3 mA
5 V/350 mA
24 V/350 mA
500 kHz,
30 m (98 ft.) shielded
cable length
100 kHz for
25 m (82 ft.) cable
length shielded
25 kHz for 100 m
(330 ft.) cable length
shielded
2 pulse series 90
degrees out of phase
1 zero pulse
±30 V
no
- 30 V to +5 V
13 V to 30 V
1.5 mA
7.3 mA
20 V to 30 V
no
100 mA
short-circuit proof output
100 m (330 ft.)
4.7 V to 5.5 V
180 mA
15-45