Siemens S5-100U User Manual page 371

Simatic s5 programmable controller
Hide thumbs Also See for S5-100U:
Table of Contents

Advertisement

S5-100U
Digital Output Module 8 x 24 V DC/1 A
1
F
2
4
.0
3
.1
6
.2
5
.3
8
.4
7
.5
10
.6
9
.7
DIGITAL OUTPUT
8 x 24 V DC/1 A
6ES5 451-8MA11
1 2
3
4
5
1
3
5
2
4
L+
M
X.1 X.0 X.3 X.2 X.5 X.4 X.7 X.6
EWA 4NEB 812 6120-02
L+
M
5
6
+9 V
GND
Data
7
9
6
8
10
Technical specifications
Address designation
(for ET 100U only)
Number of outputs
Galvanic isolation
- in groups of
Load voltage L+
- rated value
- permissible range
(including ripple)
- value at t<0.5 s
Output current for
"1" signal
- rated value
- permissible range
- lamp load
max. 12 W
Residual current at
"0" signal
max. 1.0 mA
Output voltage
- at "1" signal
max. L+ (- 0.8 V)
Short-circuit
protection
Fault LED (red)
Voltage induced on
circuit interruption
(internal) limited to
Switching frequency
- resistive load
max. 100 Hz
- inductive load
max. 2 Hz
Permissible current
of all outputs
Driving of
digital input
Paralleling of 2
outputs
- maximum current
Permissible ambient
temperature of module
- horizontal arrangement
- vertical arrangement
Length of cable
- unshielded
max. 100 m (330 ft.)
Insulation rating
Rated insulation voltage
(+ 9 V to L+)
- insulation group
- tested with
Rated insulation voltage
(+ 9 V to
)
- insulation group
- tested with
Current consumption
- from +9 V (CPU)
typ.
- from L+ (without load) typ.
Power loss
of the module
typ.
Weight
approx.
Module Spectrum
(6ES5 451-8MA11)
8 DQ
8
yes (optocoupler)
8
24 V DC
20 to 30 V
35 V
1 A
5 mA to 1A
short-circuit protected
output with autom.
switch on when the
short-circuit does not
exist any more
short-circuit
-15 V
6 A
possible
possible
1.8 A
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
VDE 0160
24 V AC
2 x B
500 V AC
12 V AC
1 x B
500 V AC
24 mA
200 mA
4 W
230g (8 oz.)
14-27

Advertisement

Table of Contents
loading

Table of Contents