Siemens S5-100U User Manual page 375

Simatic s5 programmable controller
Hide thumbs Also See for S5-100U:
Table of Contents

Advertisement

S5-100U
Relay Output Module 4 x 30 V DC/230 V AC
3
.0
.4
4
5
.1
.5
6
.2
7
.6
8
.3
9
.7
10
RELAY OUTPUT
4 x 30 V DC/230 V AC
6ES5 452-8MR11
1
2
3
4
5
1
3
5
2
4
L+
M
X.0
X.1
EWA 4NEB 812 6120-02
L+
1
M
2
7
6
+9 V
GND
Data
7
9
6
8
10
X.2
X.3
Technical specifications
Address designation
(for ET 100U only)
Outputs
Galvanic isolation
- in groups of
Continuous current I
th
Relay type
Switching capacity
of the contacts
- resistive load
max.
- inductive load
max.
Operating cycle of
the contacts according to
VDE 0660, part 200
- AC-11
- DC-11
Switching frequency
max.
Permissible ambient
temperature of module
- horizontal arrangement
- vertical arrangement
Length of cable
- unshielded
max.
Insulation rating
Rated insulation voltage
(+ 9 V to L1)
- insulation group
- tested with
Rated insulation voltage
(+ 9 V to
)
- insulation group
- tested with
Rated insulation voltage
(between contacts)
- insulation group
- tested with
Supply voltage L+
(for the relay)
- rated value
- ripple V
max.
pp
- permissible range
(ripple included)
- value at t<0.5 s
Current consumption
- from + 9 V (CPU)
typ.
- from L+
typ.
Power loss of
the module
typ.
Weight
approx.
Module Spectrum
(6ES5 452-8MR11)
4 DQ
4 relay outputs,
contact switching
varistor SIOV-S07-
K275
yes (optocoupler)
1
5 A
Siemens
V 23127-D 0006-
A402
5 A at 250 V AC
2.5 A at 30 V DC
1.5 A at 250 V AC
0.5 A at 30 V DC
6
1.5 x 10
0.5 x 10
6
10 Hz
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
100 m (330 ft.)
VDE 0160
250 V AC
2 x B
1500 V AC
12 V AC
1 x B
500 V AC
250 V AC
2 x B
1500 V AC
24 V DC
3.6 V
20 to 30 V
35 V
14 mA
100 mA
2 W
240 g (8 oz.)