Prompt Time Sequence
Bit 13 in the status word is set after the prompt time has elapsed.
Bit 13 remains set until you reset it in the control program.
The prompt time can be read at any time.
Caution
!
If the prompt time is reached in the STOP mode or during Power OFF, the prompt time
cannot be evaluated. It is always deleted on restart.
Example:
Setting and evaluating the prompt time
In the example program, the status of input I 0.6 determines whether the settings for the prompt time
are transferred. Before setting input I 0.6, you must transfer the settings to flag bytes FY130 and
FY135. Enter values that you do not wish to be evaluated as FF
You set the clock mode with input I 1.0. Use input I 0.1 to specify the the AM/PM bit for 12-hour
mode.
If the preset prompt time has been reached, set flag F 13.2. If errors are made while entering the
prompt time, the error bit, flag F 12.2, is set.
The clock data is stored in DB2 beginning with data word DW0, and the status word is flag word
FW10.
OB1 STL
:
:
:
:
:
:A
I
0.6
:S
F
20.1
:JU
FB
11
NAME :SET PROMPT TIME
WDAY :
FY 130
DAY
:
FY 131
MON
:
FY 132
HOUR :
FY 133
AMPM :
I
0.1
MIN
:
FY 134
SEC
:
FY 135
ERR
:
F
12.2
ALRM :
F
13.2
MODE :
I
1.0
:BE
EWA 4NEB 812 6120-02
.
H
Explanation
=========================================
SETTING AND EVALUATING THE PROMPT TIME
=========================================
LOAD VALUES INTO FY130 TO FY135
FIRST.
TRIGGER SETTING OF PROMPT TIME
BY SETTING F 20.1 (RESET IN FB11)
(SET AND EVALUATING PROMPT TIME)
WEEKDAY
DAY
MONTH
HOUR
AMPM-BIT (ONLY IMPORTANT IN 12-HOUR MODE)
MINUTES
SECONDS
ERROR BIT
DISPLAYS THAT PROMPT TIME IS REACHED.
12-HOUR MODE: I 33.0 = 1
The Integral Real-Time Clock
12-27