STEP 5 Operations
Pulse
Example:
Output Q 1.0 is set when the signal state at input I 0.0 changes from "0" to "1".
However, the output should not remain set longer than 5 s.
Signal states
1
0
1
0
5
STL
A
I
0.0
L
KT 500.0
SP
T
1
NOP 0
NOP 0
NOP 0
A
T
1
=
Q
1.0
Note
The time tolerance is equivalent to the time base. Always use the smallest time base
possible.
8-20
Timing Diagram
CSF
T 1
1
I 0.0
KT 500.0
TV
BI
DE
R
Q
I 0.0
T 1
Q 1.0
Time in s
Time relay with transitional
T 1:
NO contact
KT 500.0
Q 1.0
Circuit Diagram
I 0.0
Q 1.0
LAD
T 1
I 0.0
1
TV
BI
DE
R
Q
Q 1.0
EWA 4NEB 812 6120-02