Mode Of Operation For The External I/O Bus; The S5-100U; Structure Of The External I/O Bus - Siemens S5-100U User Manual

Simatic s5 programmable controller
Hide thumbs Also See for S5-100U:
Table of Contents

Advertisement

Technical Description
2.2.2

Mode of Operation for the External I/O Bus

The S5-100U has a serial bus for the transfer of data between the CPU and the I/O modules. This
serial bus has the following characteristics:
The modular design permits optimal adaptation to the particular control task.
No addresses have to be set on the I/O modules.
A terminating resistor connector is not required.
Direct access to individual modules is not possible.
A number of shift registers moves the data (Figure 2-5).
Four data bits and one check bit for bus monitoring are assigned to each slot in the bus unit. All
modules requiring more than four data bits have their own shift register and therefore do not have to
use the shift register of the particular slot.
Shift register
of a slot
Shift register of an
8-channel digital module
or of an analog module
2-6
Slot number
CPU
0
Figure 2-5. Structure of the External I/O Bus
Data ring bus
1
2
5 Bits
n x 5 Bits
n=2, 4, 6 to 16
S5-100U
3
EWA 4NEB 812 6120-02