3-1-2.

MULTIPLE OUTDOOR UNIT INSTALLATION

Provide at least 25mm of space between the outdoor units if multiple units are installed.
When routing the piping from the side of an outdoor unit, provide space for the piping.
No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following
example when an obstruction is present also in the upward area.
WHEN THE UPWARD AREA IS OPEN
Obstacles at rear only
WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD
AREA
Obstacles at rear and above only
1500
3-1-3.

OUTDOOR UNITS INSTALLATION IN MULTI ROW

Single parallel unit arrangement
600
1000
Obstacles at front only
300
1500
500
Max. 300
150
2000 or more
- (03 - 07) -
Obstacles at front and rear only
1500 or more
Multiple parallel unit arrangement
600
1500
3. OUTDOOR UNIT & BRANCH BOX
Unit : mm
500
1500 or more
500
3000 or more