PEAK CUT MODE
Operation that suppressed the current value can be performed by means of the following on-
site work. The air conditioner is set to the Peak cut mode when closing the contact input of a
commercial ON/OFF switch to a connector on the outdoor control PC board.
Circuit diagram example
Outdoor unit
control PC board
Connector
1
2
* Make the distance from the PC board to the connected unit within 10 m.
Contact capacity: DC 24 V or more, 10 mA or more.
Use the following parts and construct a circuit as shown above.
nput igna
Pea cut
*Set the "Peak cut mode" level, refer to "5. FUNCTION SETTING".
ON
Input Signal
OFF
ON
Peak cut mode
OFF
Parts (Optional)
Parts name
Model name
Connected unit
Ex.) Switch
*10 m
Signal
Field supply
ode nput igna
External connect kit
UTY-XWZXZ3
- (06 - 107) -
or a operation
6. SYSTEM DESIGN