Fujitsu AUYG07LVLA Design & Technical Manual page 334

Hide thumbs Also See for AUYG07LVLA:
Table of Contents

Advertisement

8) Auto restart
Enable or disable automatic restart after a power interruption.
Setting description
Enable
Disable
*Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external device.
9) Room temperature sensor switching
(Only for Wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
Setting description
Indoor unit
Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller is active.
*Remote controller sensor must be turned on by using the remote controller.
10) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
Setting description
A
B
C
D
11) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Setting description
Operation/Stop mode
(Setting prohibited)
Forced stop mode
12) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
"Wired remote controller" (01). This function will only work if the function setting 42 is set at
"Both" (01)
Setting description
Both
Wired remote controller
( ... Factory setting)
Function number
Setting value
40
( ... Factory setting)
Function number
Setting value
42
( ... Factory setting)
Function number
Setting value
44
( ... Factory setting)
Function number
Setting value
46
( ... Factory setting)
Function number
Setting value
48
- (06 - 86) -
00
01
00
01
00
01
02
03
00
01
02
00
01
6. SYSTEM DESIGN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents