Fujitsu AUYG07LVLA Design & Technical Manual page 279

Hide thumbs Also See for AUYG07LVLA:
Table of Contents

Advertisement

Straight pipe length
When connecting the main piping, do not bend
it near the connection section.
If the main pipe must be bent due to unavoidable
circumstances, ensure that the linear section is
150mm or more.
HEAT INSULATION INSTALLATION
After connection the pipes, use the supplied heat insulation to insulate them.
Remove the protective sheet from the double-stick tape that is affi xed to the heat insulation.
Use tape (field supply) to seal the seam so that there will be no gap at the junction between the
aforementioned heat insulation and coupler insulation, and between coupler insulation and the
heat insulation on the local piping.
ape fie d supp
Coupler insulation
(Gas pipe ... Large)
(Liquid pipe ... Small)
Be sure to install the heat insulation on liquid pipes and gas pipes. Unless they are thermally
insulated, water condensation can cause accidents or reduction in performance.
After installing the heat insulation, if you worry about possible condensation due to the high
humidity of installation position, please use locally procured heat insulation to reinforce insulation.
Coupler insulation
ape fie d supp
ape fie d supp
CAUTION
- (06 - 31) -
to branch box
R
to outdoor unit
ape fie d supp
Insulation
No gap
ape fie d supp
Heat insulation
fie d supp
to branch box
Straight pipe=150mm or
more
6. SYSTEM DESIGN