STOP OPERATION MODE
It is possible to switch to Batch stop or Emergency stop and Normal operation by using external
input.
Circuit diagram example
Outdoor unit
control PC board
Connector
1
2
* Make the distance from the PC board to the connected unit within 10 m.
Contact capacity: DC 24 V or more, 10 mA or more.
Use the following parts and construct a circuit as shown above.
* Set the "Batch stop" or "Emergency stop" pattern, refer to "5. FUNCTION SETTING"
When function setting is in "Batch stop" mode
Input signal
Batch stop
Command
Operation
Air conditioner
Remote controller
Connected unit
Ex.) Switch
*10 m
Signal
Field supply
ON
OFF
Normal
Stop
- (06 - 108) -
ON
ON
Remote control
operation validity
6. SYSTEM DESIGN