AIR CONDITIONER
Simultaneous multi
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
AUYG18LVLB × 4
AUYG30LRLE × 3
AUYG22LVLA × 4
AUYG36LRLE × 2
AUYG24LVLA × 3
AUYG45LRLA × 2
ABYG18LVTB × 4
ABYG30LRTE × 3
ABYG22LVTA × 4
ABYG36LRTE × 2
ABYG24LVTA × 3
ABYG45LRTA × 2
AOYG72LRLA
AOYG90LRLA
ARYG18LLTB × 4
ARYG22LMLA × 4
ARYG24LMLA × 3
ARYG30LMLE × 3
ARYG36LMLE × 2
ARYG45LMLA × 2
DR_SM001EF_05
2021.01.08

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu AUYG18LVLB

  • Page 1 AIR CONDITIONER Simultaneous multi DESIGN & TECHNICAL MANUAL AUYG18LVLB × 4 AUYG30LRLE × 3 ARYG18LLTB × 4 ARYG22LMLA × 4 AUYG22LVLA × 4 AUYG36LRLE × 2 ARYG24LMLA × 3 AUYG24LVLA × 3 AUYG45LRLA × 2 ARYG30LMLE × 3 INDOOR ARYG36LMLE × 2 ARYG45LMLA ×...
  • Page 2 Notices: • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Copyright © 2017, 2021 Fujitsu General Limited. All rights reserved.
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNITS ................1 1. Model lineup ....................2 2. Specifications....................3 2-1. Compact cassette type ....................3 2-2. Cassette type ........................4 2-3. Slim duct type ........................5 2-4. Duct type..........................6 2-5. Floor/Ceiling type ......................8 2-6. Ceiling type ........................9 3. Dimensions....................10 3-1. Compact cassette type ....................10 3-2.
  • Page 4 CONTENTS (continued) 8-2. Cassette type .......................121 8-3. Slim duct type ......................123 8-4. Duct type........................124 8-5. Floor/Ceiling type ......................127 8-6. Ceiling type ........................129 8-7. Sound level check point ....................131 9. Electrical characteristics ................135 10. Safety devices ...................136 11. Accessories ....................137 11-1.Compact cassette type ....................137 11-2.Cassette type ......................138 11-3.Slim duct type ......................139 11-4.Duct type........................140...
  • Page 5 CONTENTS (continued) Part 2. OUTDOOR UNIT..............143 1. Specifications....................144 2. Dimensions....................145 2-1. Models: AOYG72LRLA and AOYG90LRLA..............145 3. Installation space ..................146 3-1. Models: AOYG72LRLA and AOYG90LRLA..............146 4. Refrigerant circuit ..................149 4-1. Models: AOYG72LRLA and AOYG90LRLA..............149 5. Wiring diagrams ..................152 5-1. Models: AOYG72LRLA and AOYG90LRLA..............152 6.
  • Page 6 CONTENTS (continued) Part 3. SYSTEM DESIGN..............173 1. Installation precautions ................174 1-1. Indoor unit installation precautions................174 1-2. Outdoor unit installation precautions ................178 2. Pipe design ....................179 2-1. Important items when using refrigerant (R410A)............179 2-2. Piping limitation......................180 2-3. Pipe size ........................187 2-4. Selection of pipe heat insulating material..............189 2-5.
  • Page 7 CONTENTS (continued) 9. Check and test...................294 9-1. Test run........................294 9-2. Error code ........................296 9-3. Pump down........................297 10. Optional parts installation ................299 10-1.Drain pump unit for duct type (UTZ-PX1NBA) ............299 10-2.Drain pump unit for ceiling type (UTR-DPB24T) ............302 10-3.Fresh air intake kit for cassette type (UTZ-VXRA) ............303 10-4.Fresh air intake kit for compact cassette type (UTZ-VXAA) ........313 10-5.Auto louver grille kit (UTD-GXTB-W) ................322...
  • Page 8 CONTENTS (continued) Part 4. OPTIONAL PARTS...............325 1. Branch pipes .....................326 1-1. Model: UTP-SX272A....................326 1-2. Model: UTP-SX372A....................327 1-3. Model: UTP-SX236A....................328 1-4. Model: UTP-SX254A....................329 2. Controllers ....................330 2-1. Lineup ..........................330 2-2. Parts ..........................331 3. Cassette grille....................332 3-1. Lineup ..........................332 3-2. Parts ..........................332 4.
  • Page 9: Part 1. Indoor Units

    Part 1. INDOOR UNITS COMPACT CASSETTE FLOOR/CEILING TYPE: TYPE: AUYG18LVLB ABYG18LVTB AUYG22LVLA ABYG22LVTA AUYG24LVLA ABYG24LVTA CASSETTE TYPE: CEILING TYPE: AUYG30LRLE ABYG30LRTE AUYG36LRLE ABYG36LRTE AUYG45LRLA ABYG45LRTA SLIM DUCT TYPE: ARYG18LLTB DUCT TYPE: ARYG22LMLA ARYG24LMLA ARYG30LMLE ARYG36LMLE ARYG45LMLA...
  • Page 10: Model Lineup

    Outdoor unit 36 kBtu/h × 2 24 kBtu/h × 3 18 kBtu/h × 4 ARYG36LMLE ARYG24LMLA ARYG18LLTB AOYG72LRLA AUYG36LRLE AUYG24LVLA AUYG18LVLB ABYG36LRTE ABYG24LVTA ABYG18LVTB Indoor unit Twin Triple Double twin Outdoor unit 45 kBtu/h × 2 30 kBtu/h × 3 22 kBtu/h ×...
  • Page 11: Specifications

    2. Specifications 2-1. Compact cassette type Model name AUYG18LVLB AUYG22LVLA AUYG24LVLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Turbo fan × 1 Motor output...
  • Page 12: Cassette Type

    2-2. Cassette type Model name AUYG30LRLE AUYG36LRLE AUYG45LRLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V HIGH 1,600 1,800 1,900 1,400 1,400 1,640 Cooling 1,270 1,270 1,460 QUIET 1,150 1,150 1,250 Airflow rate HIGH 1,600 1,800 1,900 1,400 1,400...
  • Page 13: Slim Duct Type

    2-3. Slim duct type Model name ARYG18LLTB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco fan × 3 Motor output Recommended static pressure 0 to 90 HIGH Cooling QUIET...
  • Page 14: Duct Type

    2-4. Duct type Model name ARYG22LMLA ARYG24LMLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V HIGH 1,100 Cooling QUIET Airflow rate HIGH 1,100 Heating QUIET Type × Q'ty Sirocco fan × 2 Motor output Recommended static pressure 30 to 150 HIGH Cooling...
  • Page 15 Model name ARYG30LMLE ARYG36LMLE ARYG45LMLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V HIGH 1,900 2,100 1,620 1,750 Cooling 1,270 1,350 QUIET 1,070 Airflow rate HIGH 2,100 2,100 1,620 1,750 Heating 1,270 1,350 QUIET 1,070 Type × Q'ty Sirocco fan ×...
  • Page 16: Floor/Ceiling Type

    2-5. Floor/Ceiling type Model name ABYG18LVTB ABYG22LVTA ABYG24LVTA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco fan × 2 Motor output 44 (Floor console) 49 (Floor console) HIGH 43 (Under ceiling)
  • Page 17: Ceiling Type

    2-6. Ceiling type Model name ABYG30LRTE ABYG36LRTE ABYG45LRTA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V HIGH 1,660 1,900 2,100 1,500 1,500 1,700 Cooling 1,200 1,200 1,400 QUIET 1,000 1,000 1,100 Airflow rate HIGH 1,660 1,900 2,100 1,500 1,500...
  • Page 18: Dimensions

    3. Dimensions 3-1. Compact cassette type ¢ Models: AUYG18LVLB, AUYG22LVLA, and AUYG24LVLA Unit: mm • Cassette grille mounting state 530: Hanging bolt position op view Be sure to leave Service access service access for future service at the designated position.
  • Page 19  Installation space requirement Unit: mm Strong and durable ceiling or more 1,000 1,000 or more or more 1,800 or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) Standard 2,700 High ceiling 3,000 3-way direction setting: Unit: mm 100 or more* NOTES: •...
  • Page 20: Cassette Type

    3-2. Cassette type ¢ Models: AUYG30LRLE, AUYG36LRLE, and AUYG45LRLA Hanging bolt position Drain hose View A Ceiling Wire hole Fresh air inlet (cut out) Ø95 View B View C 4 × Ø3.2 hole - 12 - 3-2. Cassette type 3. Dimensions...
  • Page 21 ¢ Installation space requirement Unit: mm Strong and durable ceiling 256 or more 1,500 3,000 or more or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) Mode AUYG30LRLE AUYG36LRLE AUYG45LRLA 2,700 Standard 3,200 High ceiling 3,600 4,200 3-way direction setting: Unit: mm 100 or more*...
  • Page 22: Slim Duct Type

    3-3. Slim duct type ¢ Model: ARYG18LLTB Unit: mm Rear view View A Drain port 100 × 8 = 800 Top view Side view Front view Bottom view - 14 - 3-3. Slim duct type 3. Dimensions...
  • Page 23 ¢ Installation space requirement Provide sufficient installation space for product safety. In ceiling-concealed installations: Unit: mm 300 or more Strong and durable ceiling 20 or more Indoor unit Left Right side side 20 or more Service access Ceiling or more or more Floor In wall-concealed installations:...
  • Page 24 ¢ Maintenance space requirement For future maintenance and service access, provide sufficient maintenance space. NOTE: Do not place any wiring or illumination in the maintenance space, as they will impede ser- vice. Unit: mm Service access Unit Control box or more Service space - 16 - 3-3.
  • Page 25: Duct Type

    3-4. Duct type ¢ Models: ARYG22LMLA, ARYG24LMLA, ARYG30LMLE, ARYG36LMLE, and ARYG45LMLA Unit: mm Front view Side view (L) Side view (R) Top view Rear view • When using a square duct Unit: mm P176 x 6 = 1,044 Ø 3.2 - 17 - 3-4.
  • Page 26 • Bottom air intake hole Unit: mm 1,015 ¢ Installation space requirement Unit: mm 2,500 or more (When no ceiling) 300 or more 150 or more Floor ¢ Maintenance space requirement • It shall be possible to install and remove the control box. Unit: mm Service access 300 or more...
  • Page 27: Floor/Ceiling Type

    3-5. Floor/Ceiling type ¢ Models: ABYG18LVTB, ABYG22LVTA, and ABYG24LVTA Unit: mm Hole for lifting bolt (Use M10 screw bolt.) ø45-mm hole Side view Rear view Bottom view Wall bracket Side of unit ø100 hole ø50 hole - 19 - 3-5. Floor/Ceiling type 3.
  • Page 28  Installation space Unit: mm Left Right 300 or more 300 or more Ceiling Left Right Indoor unit 150 or more 300 or more Ceiling 20 or more Obstruction Floor - 20 - 3-5. Floor/Ceiling type 3. Dimensions...
  • Page 29: Ceiling Type

    3-6. Ceiling type ¢ Models: ABYG30LRTE, ABYG36LRTE, and ABYG45LRTA Unit: mm 1,600 Top view Side view Rear view Dimensions 1,600 (Space Required for Installation) INDOOR UNIT (Top view) Suspension bolt should extend INDOOR UNIT outward 30 to 75. Suspension bolt pitch - 21 - 3-6.
  • Page 30 ¢ Installation space requirement Unit: mm Indoor unit 80 or more 150 or more Ceiling 10 or more Obstruction Floor Ceiling panel Indoor unit Ceiling panel 80 or more 150 or more 10 or more Obstruction Floor - 22 - 3-6.
  • Page 31: Wiring Diagrams

    4. Wiring diagrams 4-1. Compact cassette type ¢ Models: AUYG18LVLB, AUYG22LVLA, and AUYG24LVLA - 23 - 4-1. Compact cassette type 4. Wiring diagrams...
  • Page 32: Cassette Type

    4-2. Cassette type ¢ Models: AUYG30LRLE, AUYG36LRLE, and AUYG45LRLA - 24 - 4-2. Cassette type 4. Wiring diagrams...
  • Page 33: Slim Duct Type

    4-3. Slim duct type ¢ Model: ARYG18LLTB - 25 - 4-3. Slim duct type 4. Wiring diagrams...
  • Page 34: Duct Type

    4-4. Duct type ¢ Models: ARYG22LMLA and ARYG24LMLA - 26 - 4-4. Duct type 4. Wiring diagrams...
  • Page 35 ¢ Models: ARYG30LMLE, ARYG36LMLE, and ARYG45LMLA - 27 - 4-4. Duct type 4. Wiring diagrams...
  • Page 36: Floor/Ceiling Type

    4-5. Floor/Ceiling type ¢ Models: ABYG18LVTB, ABYG22LVTA, and ABYG24LVTA - 28 - 4-5. Floor/Ceiling type 4. Wiring diagrams...
  • Page 37: Ceiling Type

    4-6. Ceiling type ¢ Models: ABYG30LRTE, ABYG36LRTE, and ABYG45LRTA - 29 - 4-6. Ceiling type 4. Wiring diagrams...
  • Page 38: Air Velocity And Temperature Distributions

    5. Air velocity and temperature distributions 5-1. Compact cassette type ¢ Model: AUYG18LVLB (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25...
  • Page 39 ¢ Model: AUYG18LVLB (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25...
  • Page 40 ¢ Model: AUYG22LVLA (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s...
  • Page 41 ¢ Model: AUYG22LVLA (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view...
  • Page 42 ¢ Model: AUYG24LVLA (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s...
  • Page 43 ¢ Model: AUYG24LVLA (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view...
  • Page 44: Cassette Type

    5-2. Cassette type ¢ Model: AUYG30LRLE (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 0.25 0.25 Top view Vertical airflow direction louver: Upward 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s...
  • Page 45 ¢ Model: AUYG30LRLE (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view 0.25 0.25 Vertical airflow direction louver: Upward Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view...
  • Page 46 ¢ Model: AUYG36LRLE (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s Top view Vertical airflow direction louver: Upward Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Downward 0.25...
  • Page 47 ¢ Model: AUYG36LRLE (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view 0.25 0.25 Vertical airflow direction louver: Upward Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view...
  • Page 48 ¢ Model: AUYG45LRLA (4-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view 0.25 0.25 Vertical airflow direction louver: Upward 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s...
  • Page 49 ¢ Model: AUYG45LRLA (3-way air outlet) Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view 0.25 0.25 Vertical airflow direction louver: Upward Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view...
  • Page 50: Slim Duct Type

    5-3. Slim duct type ¢ Model: ARYG18LLTB NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 51 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 52: Floor/Ceiling Type

    5-4. Floor/Ceiling type ¢ Model: ABYG18LVTB (Under ceiling) Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up 0.25 Horizontal airflow direction louver: Center Unit: m/s 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
  • Page 53 ¢ Model: ABYG18LVTB (Floor console) Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Down 0.25 Horizontal airflow direction louver: Center Unit: m/s 0.25 Top view Vertical airflow direction louver: Down Horizontal airflow direction louver: Left & Right 0.25 Unit: m/s Side view...
  • Page 54 ¢ Model: ABYG22LVTA (Under ceiling) Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up 0.25 Horizontal airflow direction louver: Center Unit: m/s 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Unit: m/s Side view...
  • Page 55 ¢ Model: ABYG22LVTA (Floor console) Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view 0.25 Vertical airflow direction louver: Down Horizontal airflow direction louver: Center Unit: m/s 0.25 Top view Vertical airflow direction louver: Down Horizontal airflow direction louver: Left & Right 0.25 Unit: m/s Side view...
  • Page 56 ¢ Model: ABYG24LVTA (Under ceiling) Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up 0.25 Horizontal airflow direction louver: Center Unit: m/s 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Unit: m/s Side view...
  • Page 57 ¢ Model: ABYG24LVTA (Floor console) Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view 0.25 Vertical airflow direction louver: Down Horizontal airflow direction louver: Center Unit: m/s 0.25 Top view Vertical airflow direction louver: Down Horizontal airflow direction louver: Left & Right 0.25 Unit: m/s Side view...
  • Page 58: Ceiling Type

    5-5. Ceiling type ¢ Model: ABYG30LRTE Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up 0.25 Horizontal airflow direction louver: Center Unit: m/s 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Unit: m/s 0.25...
  • Page 59 ¢ Model: ABYG36LRTE Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up 0.25 Horizontal airflow direction louver: Center Unit: m/s 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Unit: m/s 0.25...
  • Page 60 ¢ Model: ABYG45LRTA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up 0.25 Horizontal airflow direction louver: Center Unit: m/s 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Unit: m/s 0.25...
  • Page 61: Fan Performance

    6. Fan performance 6-1. Slim duct type ¢ Model: ARYG18LLTB SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) SP mode 00 Hi (Normal SP) upper limit Hi (SP mode 00) Quiet (SP mode 00)
  • Page 62  Characteristics of air volume and capacity • Cooling Capacity 1,000 1,100 Airflow (m • Heating Capacitty 1,000 1,100 Airflow (m - 54 - 6-1. Slim duct type 6. Fan performance...
  • Page 63: Duct Type

    6-2. Duct type ¢ Model: ARYG22LMLA (Normal mode) Static pressure (Pa) m3/h — — — — — 1,200 1,100 1,000 HIGH — — — — — — — — — — m3/h — — — — — — — — —...
  • Page 64 • Cooling Capacity 1,000 1,100 1,200 1,300 Airflow (m • Heating Capacity 1,000 1,100 1,200 1,300 Airflow (m - 56 - 6-2. Duct type 6. Fan performance...
  • Page 65 ¢ Model: ARYG22LMLA (Static pressure mode 1) Static pressure (Pa) m3/h — — — — — — 1,200 1,000 HIGH — — — — — — — — — — — — m3/h — — — — 1,000 — — —...
  • Page 66 • Cooling Capacity 1,000 1,100 1,200 1,300 Airflow (m • Heating Capacity 1,000 1,100 1,200 1,300 Airflow (m - 58 - 6-2. Duct type 6. Fan performance...
  • Page 67 ¢ Model: ARYG22LMLA (Static pressure mode 2) Static pressure (Pa) m3/h — — — — — — 1,160 HIGH — — — — — — — — — — — — m3/h — — — — 1,020 — — — —...
  • Page 68 • Cooling Capacity 1,000 1,100 1,200 1,300 Airflow (m • Heating Capacity 1,000 1,100 1,200 1,300 Airflow (m - 60 - 6-2. Duct type 6. Fan performance...
  • Page 69 ¢ Model: ARYG22LMLA (Static pressure mode 3) Static pressure (Pa) m3/h — — — — — — 1,100 HIGH — — — — — — — — — — — — m3/h — — — — 1,000 — — — —...
  • Page 70 • Cooling Capacity 1,000 1,100 1,200 1,300 Airflow (m • Heating Capacity 1,000 1,100 1,200 1,300 Airflow (m - 62 - 6-2. Duct type 6. Fan performance...
  • Page 71 ¢ Model: ARYG24LMLA (Normal mode) Static pressure (Pa) m3/h — — — — — 1,200 1,100 1,000 HIGH — — — — — — — — — — m3/h — — — — — — — — — — — —...
  • Page 72 • Cooling Capacity 1,000 1,100 1,200 1,300 Airflow (m • Heating Capacity 1,000 1,100 1,200 1,300 Airflow (m - 64 - 6-2. Duct type 6. Fan performance...
  • Page 73 ¢ Model: ARYG24LMLA (Static pressure mode 1) Static pressure (Pa) m3/h — — — — — — 1,200 1,000 HIGH — — — — — — — — — — — — m3/h — — — — 1,000 — — —...
  • Page 74 • Cooling Capacity 1,000 1,100 1,200 1,300 Airflow (m • Heating Capacity 1,000 1,100 1,200 1,300 Airflow (m - 66 - 6-2. Duct type 6. Fan performance...
  • Page 75 ¢ Model: ARYG24LMLA (Static pressure mode 2) Static pressure (Pa) m3/h — — — — — — 1,160 HIGH — — — — — — — — — — — — m3/h — — — — 1,020 — — — —...
  • Page 76 • Cooling Capacity 1,000 1,100 1,200 1,300 Airflow (m • Heating Capacity 1,000 1,100 1,200 1,300 Airflow (m - 68 - 6-2. Duct type 6. Fan performance...
  • Page 77 ¢ Model: ARYG24LMLA (Static pressure mode 3) Static pressure (Pa) m3/h — — — — — — 1,100 HIGH — — — — — — — — — — — — m3/h — — — — 1,000 — — — —...
  • Page 78 • Cooling Capacity 1,000 1,100 1,200 1,300 Airflow (m • Heating Capacity 1,000 1,100 1,200 1,300 Airflow (m - 70 - 6-2. Duct type 6. Fan performance...
  • Page 79 ¢ Model: ARYG30LMLE (Normal mode) Static pressure (Pa) m3/h — — — — — 2,270 2,240 2,100 HIGH — — — — — (Heating) — — — — — 1,336 1,318 1,236 m3/h — — — — — 2,050 2,020 1,900 HIGH —...
  • Page 80 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 72 - 6-2. Duct type 6. Fan performance...
  • Page 81 ¢ Model: ARYG30LMLE (Static pressure mode 1) Static pressure (Pa) m3/h — — — — — 1,950 1,860 1,700 HIGH — — — — — — — — — — 1,148 1,095 1,001 m3/h — — — — 1,730 1,620 1,520 —...
  • Page 82 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 74 - 6-2. Duct type 6. Fan performance...
  • Page 83 ¢ Model: ARYG30LMLE (Static pressure mode 2) Static pressure (Pa) m3/h — — — — — — 1,850 1,600 HIGH — — — — — — — — — — — — 1,089 m3/h — — — — 1,600 1,400 —...
  • Page 84 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 76 - 6-2. Duct type 6. Fan performance...
  • Page 85 ¢ Model: ARYG30LMLE (Static pressure mode 3) Static pressure (Pa) m3/h — — — — — — 1,730 1,500 HIGH — — — — — — — — — — — — 1,018 m3/h — — — — 1,530 1,310 —...
  • Page 86 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 78 - 6-2. Duct type 6. Fan performance...
  • Page 87 ¢ Model: ARYG36LMLE (Normal mode) Static pressure (Pa) m3/h — — — — — 2,270 2,240 2,100 HIGH — — — — — (Heating) — — — — — 1,336 1,318 1,236 m3/h — — — — — 2,050 2,020 1,900 HIGH —...
  • Page 88 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 80 - 6-2. Duct type 6. Fan performance...
  • Page 89 ¢ Model: ARYG36LMLE (Static pressure mode 1) Static pressure (Pa) m3/h — — — — — 1,950 1,860 1,700 HIGH — — — — — — — — — — 1,148 1,095 1,001 m3/h — — — — 1,730 1,620 1,520 —...
  • Page 90 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 82 - 6-2. Duct type 6. Fan performance...
  • Page 91 ¢ Model: ARYG36LMLE (Static pressure mode 2) Static pressure (Pa) m3/h — — — — — — 1,850 1,600 HIGH — — — — — — — — — — — — 1,089 m3/h — — — — 1,600 1,400 —...
  • Page 92 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 84 - 6-2. Duct type 6. Fan performance...
  • Page 93 ¢ Model: ARYG36LMLE (Static pressure mode 3) Static pressure (Pa) m3/h — — — — — — 1,730 1,500 HIGH — — — — — — — — — — — — 1,018 m3/h — — — — 1,530 1,310 —...
  • Page 94 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 86 - 6-2. Duct type 6. Fan performance...
  • Page 95 ¢ Model: ARYG45LMLA (Normal mode) Static pressure (Pa) m3/h — — — — — 2,250 2,223 2,010 HIGH — — — — — — — — — — 1,324 1,308 1,183 m3/h — — — 1,710 1,685 1,585 1,540 — —...
  • Page 96 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 88 - 6-2. Duct type 6. Fan performance...
  • Page 97 ¢ Model: ARYG45LMLA (Static pressure mode 1) Static pressure (Pa) m3/h — — — — 2,100 2,075 1,970 1,810 HIGH — — — — — — — — 1,236 1,221 1,159 1,065 m3/h — — — 1,750 1,555 1,520 — —...
  • Page 98 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 90 - 6-2. Duct type 6. Fan performance...
  • Page 99 ¢ Model: ARYG45LMLA (Static pressure mode 2) Static pressure (Pa) m3/h — — — — — — 1,900 1,660 HIGH — — — — — — — — — — — — 1,118 m3/h — — — — 1,600 1,400 —...
  • Page 100 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 92 - 6-2. Duct type 6. Fan performance...
  • Page 101 ¢ Model: ARYG45LMLA (Static pressure mode 3) Static pressure (Pa) m3/h — — — — — — 1,730 1,500 HIGH — — — — — — — — — — — — 1,018 m3/h — — — — 1,530 1,310 —...
  • Page 102 • Cooling Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m • Heating Capacity 1,100 1,300 1,500 1,700 1,900 2,100 2,300 Airflow (m - 94 - 6-2. Duct type 6. Fan performance...
  • Page 103: Airflow

    /h = 0.2778 l/s = 0.5886 CFM • 3.6 m /h = 1 l/s • 1.699 m /h = 1 CFM 7-1. Compact cassette type ¢ Model: AUYG18LVLB (Standard ceiling mode)  Cooling Fan speed Airflow HIGH QUIET  Heating...
  • Page 104 ¢ Model: AUYG18LVLB (High ceiling mode)  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 96 - 7-1. Compact cassette type 7. Airflow...
  • Page 105 ¢ Model: AUYG22LVLA (Standard ceiling mode)  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 97 - 7-1. Compact cassette type 7. Airflow...
  • Page 106 ¢ Model: AUYG22LVLA (High ceiling mode)  Cooling Fan speed Airflow 1,030 HIGH QUIET  Heating Fan speed Airflow 1,000 HIGH QUIET - 98 - 7-1. Compact cassette type 7. Airflow...
  • Page 107 ¢ Model: AUYG24LVLA (Standard ceiling mode)  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 99 - 7-1. Compact cassette type 7. Airflow...
  • Page 108 ¢ Model: AUYG24LVLA (High ceiling mode)  Cooling Fan speed Airflow 1,030 HIGH QUIET  Heating Fan speed Airflow 1,000 HIGH QUIET - 100 - 7-1. Compact cassette type 7. Airflow...
  • Page 109: Cassette Type

    7-2. Cassette type ¢ Model: AUYG30LRLE (4-way air outlet)  Cooling Fan speed Airflow 1,600 HIGH 1,400 1,270 1,150 QUIET  Heating Fan speed Airflow 1,600 HIGH 1,400 1,270 1,150 QUIET - 101 - 7-2. Cassette type 7. Airflow...
  • Page 110 ¢ Model: AUYG30LRLE (3-way air outlet)  Cooling Airflow Fan speed Max.* Min.* 1,550 1,350 HIGH 1,350 1,200 1,250 1,100 1,100 QUIET  Heating Airflow Fan speed Max.* Min.* 1,550 1,350 HIGH 1,350 1,200 1,250 1,100 1,100 QUIET *: Airflow can be changed according to the direction in which the outlet is blocked. - 102 - 7-2.
  • Page 111 ¢ Model: AUYG36LRLE (4-way air outlet in low ceiling mode)  Cooling Fan speed Airflow 1,800 HIGH 1,059 1,400 1,270 1,150 QUIET  Heating Fan speed Airflow 1,800 HIGH 1,059 1,400 1,270 1,150 QUIET - 103 - 7-2. Cassette type 7.
  • Page 112 ¢ Model: AUYG36LRLE (3-way air outlet)  Cooling Airflow Fan speed Max.* Min.* 1,700 1,550 HIGH 1,000 1,350 1,200 1,250 1,100 1,100 QUIET  Heating Airflow Fan speed Max.* Min.* 1,700 1,550 HIGH 1,000 1,350 1,200 1,250 1,100 1,100 QUIET *: Airflow can be changed according to the direction in which the outlet is blocked.
  • Page 113 ¢ Model: AUYG45LRLA (4-way air outlet)  Cooling Fan speed Airflow 1,900 HIGH 1,118 1,640 1,460 1,250 QUIET  Heating Fan speed Airflow 1,900 HIGH 1,118 1,640 1,460 1,250 QUIET - 105 - 7-2. Cassette type 7. Airflow...
  • Page 114 ¢ Model: AUYG45LRLA (3-way air outlet)  Cooling Fan speed Airflow 1,690 HIGH 1,490 1,340 1,140 QUIET  Heating Fan speed Airflow 1,690 HIGH 1,490 1,340 1,140 QUIET - 106 - 7-2. Cassette type 7. Airflow...
  • Page 115: Slim Duct Type

    7-3. Slim duct type ¢ Model: ARYG18LLTB  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 107 - 7-3. Slim duct type 7. Airflow...
  • Page 116: Duct Type

    7-4. Duct type ¢ Model: ARYG22LMLA  Cooling Fan speed Airflow 1,100 HIGH QUIET  Heating Fan speed Airflow 1,100 HIGH QUIET - 108 - 7-4. Duct type 7. Airflow...
  • Page 117 ¢ Model: ARYG24LMLA  Cooling Fan speed Airflow 1,100 HIGH QUIET  Heating Fan speed Airflow 1,100 HIGH QUIET - 109 - 7-4. Duct type 7. Airflow...
  • Page 118 ¢ Model: ARYG30LMLE  Cooling Fan speed Airflow 1,900 HIGH 1,118 1,620 1,270 QUIET  Heating Fan speed Airflow 2,100 HIGH 1,236 1,620 1,270 QUIET - 110 - 7-4. Duct type 7. Airflow...
  • Page 119 ¢ Model: ARYG36LMLE  Cooling Fan speed Airflow 1,900 HIGH 1,118 1,620 1,270 QUIET  Heating Fan speed Airflow 2,100 HIGH 1,236 1,620 1,270 QUIET - 111 - 7-4. Duct type 7. Airflow...
  • Page 120 ¢ Model: ARYG45LMLA  Cooling Fan speed Airflow 2,100 HIGH 1,236 1,750 1,030 1,350 1,070 QUIET  Heating Fan speed Airflow 2,100 HIGH 1,236 1,750 1,030 1,350 1,070 QUIET - 112 - 7-4. Duct type 7. Airflow...
  • Page 121: Floor/Ceiling Type

    7-5. Floor/Ceiling type ¢ Model: ABYG18LVTB  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 113 - 7-5. Floor/Ceiling type 7. Airflow...
  • Page 122 ¢ Model: ABYG22LVTA  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 114 - 7-5. Floor/Ceiling type 7. Airflow...
  • Page 123 ¢ Model: ABYG24LVTA  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 115 - 7-5. Floor/Ceiling type 7. Airflow...
  • Page 124: Ceiling Type

    7-6. Ceiling type ¢ Model: ABYG30LRTE  Cooling Fan speed Airflow 1,660 HIGH 1,500 1,200 1,000 QUIET  Heating Fan speed Airflow 1,660 HIGH 1,500 1,200 1,000 QUIET - 116 - 7-6. Ceiling type 7. Airflow...
  • Page 125 ¢ Model: ABYG36LRTE  Cooling Fan speed Airflow 1,900 HIGH 1,118 1,500 1,200 1,000 QUIET  Heating Fan speed Airflow 1,900 HIGH 1,118 1,500 1,200 1,000 QUIET - 117 - 7-6. Ceiling type 7. Airflow...
  • Page 126 ¢ Model: ABYG45LRTA  Cooling Fan speed Airflow 2,100 HIGH 1,236 1,700 1,000 1,400 1,100 QUIET  Heating Fan speed Airflow 2,100 HIGH 1,236 1,700 1,000 1,400 1,100 QUIET - 118 - 7-6. Ceiling type 7. Airflow...
  • Page 127: Noise Level Curve

    8. Noise level curve 8-1. Compact cassette type ¢ Model: AUYG18LVLB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15...
  • Page 128 ¢ Model: AUYG24LVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 129 8-2. Cassette type ¢ Model: AUYG30LRLE  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 QUIET NC-30 QUIET NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 130 ¢ Model: AUYG45LRLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH NC-50 NC-50 HIGH NC-45 NC-45 NC-40 NC-40 QUIET QUIET NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 131 8-3. Slim duct type ¢ Model: ARYG18LLTB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH HIGH NC-35 NC-35 NC-30 NC-30 QUIET NC-25 QUIET NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 132 8-4. Duct type ¢ Model: ARYG22LMLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH NC-35 NC-35 HIGH NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 133 ¢ Model: ARYG30LMLE  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 134 ¢ Model: ARYG45LMLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 QUIET NC-25 QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 135 8-5. Floor/Ceiling type ¢ Model: ABYG18LVTB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 136 ¢ Model: ABYG24LVTA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 137 8-6. Ceiling type ¢ Model: ABYG30LRTE  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 138 ¢ Model: ABYG45LRTA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 139 8-7. Sound level check point ¢ Compact cassette type Microphone Microphone - 131 - 8-7. Sound level check point 8. Noise level curve...
  • Page 140 ¢ Cassette type Microphone 1.5 m Microphone - 132 - 8-7. Sound level check point 8. Noise level curve...
  • Page 141 ¢ Slim duct type Measuring duct Measuring duct Set the static pressure as rating in this area Microphone Microphone Side view Front view ¢ Duct type Measuring duct Measuring duct Set the static pressure as rating in this area Microphone Microphone - 133 - 8-7.
  • Page 142 ¢ Floor/Ceiling type • Floor console Microphone Microphone • Under ceiling Microphone Microphone ¢ Ceiling type Microphone Microphone - 134 - 8-7. Sound level check point 8. Noise level curve...
  • Page 143 9. Electrical characteristics Indoor unit Power supply Wiring specification * (Total * Frequency Voltage Type Model name Connection cable (mm (Hz) AUYG18LVLB Compact AUYG22LVLA cassette AUYG24LVLA AUYG30LRLE Cassette AUYG36LRLE AUYG45LRLA Slim duct ARYG18LLTB ARYG22LMLA ARYG24LMLA Duct ARYG30LMLE ARYG36LMLE ARYG45LMLA ABYG18LVTB...
  • Page 144 10. Safety devices Indoor unit Fan motor thermal protector PCB* fuse Type Model name Activate Reset AUYG18LVLB Compact 100±10 °C 95±10 °C AUYG22LVLA cassette Fan motor stop Fan motor restart AUYG24LVLA 250 V, 3.15 A AUYG30LRLE 125±10 °C 120±10 °C...
  • Page 145 11. Accessories 11-1. Compact cassette type ¢ Models: AUYG18LVLB, AUYG22LVLA, and AUYG24LVLA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Hose band Installation manual Drain hose insulation Coupler heat insulation Remote controller (Large) Coupler heat insulation Remote controller...
  • Page 146 11-2. Cassette type ¢ Models: AUYG30LRLE, AUYG36LRLE, and AUYG45LRLA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Hose band Drain hose heat Installation manual insulation Template (Carton top) Cable tie (Large) Washer Cable tie (Small) Coupler heat insulation Wired remote controller (Large) Coupler heat insulation...
  • Page 147 11-3. Slim duct type ¢ Model: ARYG18LLTB Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie (Large) Installation manual Cable tie (Medium) Installation template Drain hose Washer Hose band Coupler heat insulation Drain hose insulation B (Large) Coupler heat insulation Remote controller (Small)
  • Page 148 11-4. Duct type ¢ Models: ARYG22LMLA, ARYG24LMLA, ARYG30LMLE, ARYG36LMLE, and ARYG45LMLA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Wired remote controller Installation manual Remote controller cable Hanger Tapping screw Coupler heat insulation Drain hose insulation (Large) Coupler heat insulation Cable tie (Large) (Small) M10 nut A...
  • Page 149 11-5. Floor/Ceiling type ¢ Models: ABYG18LVTB, ABYG22LVTA, and ABYG24LVTA Part name Exterior Q’ty Part name Exterior Q’ty M10 nut A (with flange) Operating manual For suspending the indoor unit from ceiling Cable tie (Large) Installation manual For fixing the drain hose Cable tie (Small) Cover plate (Left) For electrical wiring...
  • Page 150 11-6. Ceiling type ¢ Models: ABYG30LRTE, ABYG36LRTE, and ABYG45LRTA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie (Large) Installation manual Cable tie (Small) M10 nut A Drain hose insulation (with flange) M10 nut B VT wire (with spring lockwasher) L 280 mm Installation template...
  • Page 151 Part 2. OUTDOOR UNIT SIMULTANEOUS MULTI: AOYG72LRLA AOYG90LRLA...
  • Page 152 1. Specifications Type Inverter heat pump Model name AOYG72LRLA AOYG90LRLA Power supply 3N 400 V ~ 50 Hz Available voltage range 342—456 V Starting current 11.5 14.1 19.00 22.00 Rated Btu/h 64,800 75,000 Cooling 8.40—20.90 10.30—24.20 Min.—Max. Btu/h 28,600—71,300 35,100—82,500 Capacity 22.40 27.00...
  • Page 153 2. Dimensions 2-1. Models: AOYG72LRLA and AOYG90LRLA Unit: mm Top view 1,080 Terminal blocks (Power) Front view Side view Rear view Bottom view - 145 - 2-1. Models: AOYG72LRLA and AOYG90LRLA 2. Dimensions...
  • Page 154 3. Installation space 3-1. Models: AOYG72LRLA and AOYG90LRLA ¢ Space requirement Provide sufficient installation space for product safety.  Single outdoor unit installation • When the upper space is open: Unit: mm When there are obstacles at the rear only. When there are obstacles at the rear and sides.
  • Page 155  Multiple outdoor unit installation NOTES: • Provide at least 100 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for the piping. •...
  • Page 156  Outdoor unit installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or 500 or more more 2,000 or more 3,000 or more 600 or more 600 or more 1,000 or more 1,500 or more NOTES: •...
  • Page 157 4. Refrigerant circuit 4-1. Models: AOYG72LRLA and AOYG90LRLA ¢ Twin type Ø15.88 mm (5/8 in) × 2 Refrigerant pipe Ø25.40 mm (1 in) Pressure Check Valve Pressure sensor (High) 3-WAY Valve 4-WAY Pressure Valve Pressure sensor switch (Low) Muffler Strainer 3-WAY Expansion Valve...
  • Page 158 ¢ Triple type Ø15.88 mm (5/8 in) × 3 Refrigerant pipe Ø25.40 mm (1 in) Pressure Check Valve Pressure sensor (High) 3-WAY Valve 4-WAY Pressure Pressure Valve sensor switch (Low) Muffler Strainer 3-WAY Expansion Valve Valve : Thermistor (Compressor temperature) : Thermistor (Discharge temperature) Refrigerant pipe Ø12.70 mm (1/2 in)
  • Page 159 ¢ Double twin type 72 model: Ø12.70 mm (1/2 in) × 2 90 model: Ø15.88 mm (5/8 in) × 2 Ø15.88 mm (5/8 in) × 2 Refrigerant pipe Ø25.40 mm (1 in) Pressure Check Valve Pressure sensor (High) 3-WAY Valve 4-WAY Pressure Pressure...
  • Page 160 5. Wiring diagrams 5-1. Models: AOYG72LRLA and AOYG90LRLA - 152 - 5-1. Models: AOYG72LRLA and AOYG90LRLA 5. Wiring diagrams...
  • Page 161 6. Capacity table 6-1. Model: AOYG72LRLA TC: Total Capacity, SHC: Sensible Heat Capacity, IP: Input Power ¢ Cooling capacity (Twin)  Cassette type Model: AUYG36LRLE × 2 3,600 Indoor temperature °CDB °CWB °CDB 17.44 14.10 2.73 19.42 14.19 2.77 20.08 15.43 2.79 21.40...
  • Page 162 ¢ Heating capacity (Twin)  Cassette type Model: AUYG36LRLE × 2 3,600 Indoor temperature °CDB °CDB °CWB 10.58 5.91 10.32 6.03 10.07 6.16 9.82 6.28 9.57 6.39 16.21 6.82 15.83 6.96 15.44 7.11 15.06 7.25 14.68 7.39 18.89 7.25 18.44 7.40 18.00 7.55...
  • Page 163 ¢ Cooling capacity (Triple)  Compact cassette type Model: AUYG24LVLA × 3 2,790 Indoor temperature °CDB °CWB °CDB 17.44 12.40 2.94 19.42 12.48 2.99 20.08 13.57 3.01 21.40 13.61 3.04 22.07 14.69 3.05 23.39 14.63 3.09 24.72 15.60 3.11 17.26 12.28 2.95 19.23...
  • Page 164 ¢ Heating capacity (Triple)  Compact cassette type Model: AUYG24LVLA × 3 2,790 Indoor temperature °CDB °CDB °CWB 10.58 5.85 10.32 5.97 10.07 6.09 9.82 6.21 9.57 6.32 16.21 6.75 15.83 6.89 15.44 7.03 15.06 7.17 14.68 7.31 18.89 7.17 18.44 7.32 18.00...
  • Page 165 ¢ Cooling capacity (Double twin)  Compact cassette type Model: AUYG18LVLB × 4 2,720 Indoor temperature °CDB °CWB °CDB 17.44 13.28 2.78 19.42 13.37 2.82 20.08 14.53 2.84 21.40 14.58 2.87 22.07 15.74 2.88 23.39 15.68 2.92 24.72 16.71 2.94 17.26...
  • Page 166 ¢ Heating capacity (Double twin)  Compact cassette type Model: AUYG18LVLB × 4 3,200 Indoor temperature °CDB °CDB °CWB 10.58 5.90 10.32 6.02 10.07 6.14 9.82 6.27 9.57 6.38 16.21 6.81 15.83 6.95 15.44 7.09 15.06 7.23 14.68 7.37 18.89 7.23...
  • Page 167 6-2. Model: AOYG90LRLA TC: Total Capacity, SHC: Sensible Heat Capacity, IP: Input Power ¢ Cooling capacity (Twin)  Cassette type Model: AUYG45LRLA × 2 3,800 Indoor temperature °CDB °CWB °CDB 20.19 15.87 3.07 22.49 15.97 3.13 23.25 17.36 3.15 24.78 17.43 3.18 25.55...
  • Page 168 ¢ Heating capacity (Twin)  Cassette type Model: AUYG45LRLA × 2 3,800 Indoor temperature °CDB °CDB °CWB 12.77 6.58 12.47 6.71 12.16 6.85 11.86 6.99 11.56 7.11 19.57 7.59 19.11 7.75 18.64 7.91 18.18 8.07 17.72 8.22 22.81 8.07 22.27 8.23 21.73 8.40...
  • Page 169 ¢ Cooling capacity (Triple)  Cassette type Model: AUYG30LRLE × 3 4,800 Indoor temperature °CDB °CWB °CDB 20.19 17.51 2.75 22.49 17.62 2.79 23.25 19.15 2.81 24.78 19.22 2.84 25.55 20.75 2.85 27.08 20.66 2.89 28.62 22.02 2.91 19.98 17.33 2.76 22.27 17.44...
  • Page 170 ¢ Heating capacity (Triple)  Cassette type Model: AUYG30LRLE × 3 4,800 Indoor temperature °CDB °CDB °CWB 12.77 6.56 12.47 6.70 12.16 6.83 11.86 6.97 11.56 7.09 19.57 7.57 19.11 7.73 18.64 7.89 18.18 8.04 17.72 8.20 22.81 8.04 22.27 8.21 21.73 8.38...
  • Page 171 ¢ Cooling capacity (Double twin)  Compact cassette type Model: AUYG22LVLA × 4 3,720 Indoor temperature °CDB °CWB °CDB 20.19 15.68 3.14 22.49 15.78 3.20 23.25 17.16 3.22 24.78 17.22 3.25 25.55 18.58 3.26 27.08 18.51 3.30 28.62 19.72 3.33 19.98 15.53 3.15...
  • Page 172 ¢ Heating capacity (Double twin)  Compact cassette type Model: AUYG22LVLA × 4 3,720 Indoor temperature °CDB °CDB °CWB 12.77 6.49 12.47 6.62 12.16 6.76 11.86 6.89 11.56 7.02 19.57 7.49 19.11 7.64 18.64 7.80 18.18 7.95 17.72 8.11 22.81 7.95 22.27 8.12...
  • Page 173 7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOYG72LRLA NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 174 7-2. Model: AOYG90LRLA NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING Indoor — — — — 0.898 0.874 0.850 0.826 0.803 0.780 0.756 0.732 unit is — — — 0.938 0.913 0.889 0.864 0.840 0.817 0.793 0.769 0.744 higher —...
  • Page 175 8. Airflow 8-1. Model: AOYG72LRLA  Cooling Airflow 8,400 2,334 4,944  Heating Airflow 8,400 2,334 4,944 8-2. Model: AOYG90LRLA  Cooling Airflow 8,400 2,334 4,944  Heating Airflow 9,000 2,500 5,297 - 167 - 8-1. Model: AOYG72LRLA 8. Airflow...
  • Page 176 9. Operation noise (sound pressure) 9-1. Noise level curve ¢ Model: AOYG72LRLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 177 9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 169 - 9-2. Sound level check point 9. Operation noise (sound pressure)
  • Page 178 Indoor unit AUYG36LRLE × 2 13.2 0.7 × 2 AUYG24LVLA × 3 12.7 0.3 × 3 AUYG18LVLB × 4 12.6 0.2 × 4 ARYG36LMLE × 2 15.8 2.0 × 2 ARYG24LMLA × 3 13.9 10.6 0.7 × 3 ARYG18LLTB ×...
  • Page 179 11. Safety devices Model Type of Protection form protection AOYG72LRLA AOYG90LRLA Current protector (Filter PCB) 500 V, 45 A × 3 Circuit protection Current fuse (Main PCB) 250 V, 10 A Current fuse (Terminal) 250 V, 20 A 115±15 °C Activate Fan motor stop Fan motor...
  • Page 180 12. Accessories Part name Exterior Q’ty Part name Exterior Q’ty Installation manual Joint pipe B Drain pipe Push mount cable tie Drain cap Grommet edging Joint pipe A - 172 - 12. Accessories...
  • Page 181 Part 3. SYSTEM DESIGN...
  • Page 182 1. Installation precautions 1-1. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. ¢ Places where prohibited for use • Places where there is a danger of combustible gas leakage. •...
  • Page 183 ¢ Points to remember when installing • The product shall be installed at a place which can withstand the weight and vibration of the in- door. • To allow maintenance after refrigerant piping, drain piping, and electric wiring connection and in- stallation, provide an installation service space and an inspection port, as required.
  • Page 184 Condition Contents Countermeasures (Reference) When When the wall mounted type was installed in a bedroom, 1. Plan installation of a model installation living room, or other quiet place, the sound of the with external expansion valve. environment is refrigerant flow may be sensed as noise and must be 2.
  • Page 185 Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation strengthened) Fit tightly Heat insulating material Small exposed part Binding material (purpose is to cover the sealant) (locally purchased) of copper pipe is desirable.
  • Page 186 1-2. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. ¢ Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 187 2. Pipe design 2-1. Important items when using refrigerant (R410A) • Refrigerant piping material and wall thickness It is necessary to use seamless copper tubes for refrigerant use. Thickness of tubes are shown in table below. Nominal diameter 1-1/8 Outside diameter 6.35 9.52 12.70...
  • Page 188 2-2. Piping limitation CAUTION Keep the “piping limitation” for correct operation. • Allowable height difference: – If the height difference between indoor unit and outdoor unit is larger than the allowable value: The pressure loss will be larger → Insufficient cooling and heating Refrigerant flow noise generate at indoor The refrigerant in liquid pipe will flush →...
  • Page 189 • Twin type NOTE: Be certain to install indoor units in the same room because the combi- nations are for simultaneous opera- tion. The lengths after branching should be equal if possible. Model name (Outdoor unit) AOYG72LRLA AOYG90LRLA Model name (Indoor unit) 36 kBtu/h ×...
  • Page 190 Calculation of limitation Total Pipe length 5 m or more and 100 m or less Total 100 m or less Total 100 m or less Total 8 m or less 20 m or less 20 m or less Height difference 30 m or less 0.5 m or less - 182 -...
  • Page 191 • Triple type NOTE: Be certain to install indoor units in the same room because the combi- nations are for simultaneous opera- tion. The lengths after branching should be equal if possible. Model name (Outdoor unit) AOYG72LRLA AOYG90LRLA Model name (Indoor unit) 24 kBtu/h ×...
  • Page 192 Calculation of limitation Total Pipe length 5 m or more and 100 m or less Total 100 m or less Total 100 m or less Total 100 m or less Total 8 m or less Total 8 m or less Total 8 m or less 20 m or less...
  • Page 193 • Double twin type NOTE: Be certain to install in- door units in the same room because the combinations are for simultaneous opera- tion. The lengths after branching should be equal if possible. Model name (Outdoor unit) AOYG72LRLA AOYG90LRLA Model name (Indoor unit) 18 kBtu/h ×...
  • Page 194 Calculation of limitation Pipe length Total 5 m or more and 100 m or less L4 or L5 Total L6 or L7 Total 100 m or less 100 m or less Total 8 m or less Total 8 m or less Total 8 m or less Total...
  • Page 195 2-3. Pipe size ¢ Pipe size selection • Twin type AOYG72LRLA and AOYG90LRLA Model name (Outdoor unit) Size down Standard Liquid 12.70 (1/2) Main pipe diameter (L1) mm (in) 22.22 (7/8)* 25.40 (1) Liquid 9.52 (3/8) Branch pipe diameter (L2, L3) mm (in) 15.88 (5/8) Maximum piping length (L1 + L2 + L3)
  • Page 196 • Double twin type AOYG72LRLA AOYG90LRLA Model name (Outdoor unit) Size down Standard Size down Standard Liquid 12.70 (1/2) Main pipe diameter (First mm (in) separation) (L1) 22.22 (7/8)* 25.40 (1) 22.22 (7/8)* 25.40 (1) Liquid 9.52 (3/8) Branch pipe diameter (First mm (in) separation) (L2, L3) 15.88 (5/8)
  • Page 197 2-4. Selection of pipe heat insulating material Always insulate the refrigerant pipe to prevent condensation and water droplets by the refrigerant pipe. For selection of pipe heat insulating material, refer to following items. • Decide the thickness of the heat insulating material by referring to the recommended minimum thickness in Table 1.
  • Page 198 2-5. Additional charge calculation CAUTION • Do not turn on the power unless all operations are complete. • After evacuating the system, add refrigerant. • Do not charge the system with a refrigerant other than R410A. • Always keep to the limit on the total amount of refrigerant. Exceeding the limit on the total amount of refrigerant will lead to malfunction during charging of refrigerant.
  • Page 199 ¢ If additional refrigerant is required When the piping is longer than pre-charge length, additional charging is necessary. 1. Remove the charging cap from the liquid pipe. 2. Attach a charging pipe hose to the refrigerant cylinder, and connect it to the charging port. 3.
  • Page 200  Additional charging amount for Twin type Pre-charge length < L1 + L2 + L3 The additional charging amount will be calculated as follows. • A: Piping length (m) of liquid pipe with outside diameter of 12.70 mm (1/2 in) •...
  • Page 201  Additional charging amount for Triple type Pre-charge length < L1 + L2 + L3 + L4 The additional charging amount will be calculated as follows. • A: Piping length (m) of liquid pipe with outside diameter of 12.70 mm (1/2 in) •...
  • Page 202  Additional charging amount for Double twin type Pre-charge length < L1 + L2 + L3 + L4 + L5 + L6 + L7 The additional charging amount will be calculated as follows. • A: Piping length (m) of liquid pipe with outside diameter of 12.70 mm (1/2 in) •...
  • Page 203 3. Pipe installation 3-1. Caution of piping CAUTION Keep the permissible length of every piping limitation to prevent a defect or cooling/heating failure. • Piping material: – Use the designated size (diameter and thickness) of refrigerant pipes. – Those pipes purchased locally may contain dust inside. Blow out the dust by dried inert gas when using.
  • Page 204 CAUTION • Brazing: – While brazing the pipes, be sure to blow dry nitrogen gas through them. – If nitrogen gas is not blown through the pipes while they are being brazed, an oxidized layer may form on the inside of the pipes. If this occurs, the cooling efficiency may decrease and the air conditioner unit (compressor, valves, etc.) cause malfunction.
  • Page 205 3-2. Piping to outdoor unit ¢ Knocking out procedure in piping CAUTION • Be careful not to deform or scratch the panel while opening the knock out holes. • To protect the piping insulation after opening a knock out hole, remove any burrs from the edge of the hole.
  • Page 206 3-3. Pipe connection ¢ Precautions for connecting simultaneous operation multi CAUTION • Use genuine branch pipes for the refrigerant piping branches. Branch pipes are twin or triple type for simultaneous operation, and may be used for piping between the outdoor and indoor units.
  • Page 207 ¢ Removing the pinch pipes WARNING Remove the pinch pipe only when the internal gas is completely drained as shown on the below instructions. If gas still remains inside, the piping may crack if you melt the brazing filler metal of the junction area with burner.
  • Page 208 ¢ Connecting the pipes CAUTION • Seal the pipe route hole with putty (locally purchased) such that there are no gaps. Small in- sects or animals that are trapped in the outdoor unit may cause a short circuit in the electrical component box.
  • Page 209 ¢ Handling precautions for valves • Mounted part of blank cap is sealed for protection. • Fasten blank cap tightly after opening valves. Blank cap (mm [in]) Tightening torque (N•m [kgf•cm]) 6.35 (1/4) 20 to 25 (200 to 250) 9.52 (3/8) 20 to 25 (200 to 250) 12.70 (1/2) 28 to 32 (280 to 320)
  • Page 210 3-4. Branch pipes ¢ Branch pipe selection Indoor unit 2nd branch Indoor unit Indoor unit 1st branch 1st branch 1st branch Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Twin connection Triple connection Double twin connection Piping diameter Number of Connection...
  • Page 211 ¢ Installation procedure for Twin type and Double twin type CAUTION • Do not mistake the direction of connection. • Set the piping from the branch pipe to the indoor units to be the same length. (Max. difference: 8 • Shorten the length of the piping after branching as much as possible. (Max. length: 20 m) Check the direction of connection.
  • Page 212 Place the branch pipe in a horizontal position as far as possible. a. Only place the branch pipe as shown below during unavoidable circumstances. Horizontal position b. When connecting the main piping, do not bend it near the connection section. If the main pipe must be bent due to unavoidable circumstances, ensure that the linear section is 10 times or more than the diameter of the connection piping.
  • Page 213 After brazing the pipes, use the supplied heat insulation to insulate them. a. Remove the protective sheet from the double-stick tape that is affixed to the heat insula- tion. b. Use tape (locally purchased) to seal the seam so that there will be no gap at the junction between the aforementioned heat insulation and the heat insulation on the local piping.
  • Page 214 ¢ Installation procedure for Triple type CAUTION • Do not mistake the direction of connection. • Set the piping from the branch pipe to the indoor units to be the same length. (Max. difference: 8 • Shorten the length of the piping after branching as much as possible. (Max. length: 20 m) Check the direction of connection.
  • Page 215 Place the branch pipe in a horizontal position as far as possible. a. Only place the branch pipe as shown below during unavoidable circumstances. Liquid Horizontal position Horizontal position b. When connecting the main piping, do not bend it near the connection section. If the main pipe must be bent due to unavoidable circumstances, ensure that the linear section is 10 times or more than the diameter of the connection piping.
  • Page 216 After brazing the pipes, use the supplied heat insulation to insulate them. a. Remove the protective sheet from the double-stick tape that is affixed to the heat insula- tion. Liquid b. Use tape (locally purchased) to seal the seam so that there will be no gap at the junction between the aforementioned heat insulation and the heat insulation on the local piping.
  • Page 217 4. Wiring design 4-1. Precaution for electrical wiring Regulation on wire diameter and selecting circuit breaker size differ by locality. Install in accordance with local rules and regulations. WARNING • Wiring connections must be performed by a qualified person in accordance with the specifica- tions.
  • Page 218 WARNING • Do not start operation until the refrigerant is charged completely. The compressor will fail if it is operated before the refrigerant piping charging is complete. • Transmission cable between indoor unit and outdoor unit is 230 V. • Be sure not to remove thermistor sensor etc. from power wiring and connection wiring. Com- pressor may fail if operated while removed.
  • Page 219 4-2. Power supply cable wiring ¢ Power supply cable specifications  Indoor unit Electrical requirement Power supply cable Minimum conductor size Transmission cable Minimum conductor size 0.33 Bus wire Maximum length 500* NOTES: • *: This length shall be the total extended length in the system of the group. (Total length of bus wire and remote controller cable.) •...
  • Page 220  Wired remote controller Electrical requirement Minimum conductor size 0.33 Remote controller cable Maximum length 500* Wire type Use sheathed PVC cable, Polar 3 core NOTES: • *: This length shall be the total extended length in the system of the group. (Total length of bus wire and remote controller cable.) •...
  • Page 221 ¢ Power supply cable wiring Junction box—indoor unit (primary) 3-wires Power cable Junction box—indoor unit (secondary) 2-wires Outdoor unit 2-wires Bus wire Indoor unit—indoor unit 3-wires Remote controller cable 3-wires Example: Outdoor unit Power cable (Junction box - indoor unit Power supply Main breaker connection cable)
  • Page 222 ¢ Wiring connection rules NOTES: • Connect serial wire only to the primary unit. (If serial wire was connected from primary unit to secondary unit, the air conditioner will not operate.) • Do not loop the wiring between remote controllers. Connect only the power Do not loop the wiring cable between indoor units.
  • Page 223 ¢ Wiring method The wiring method conforms to the following diagram. 3N 400 V ~ 50 Hz 3N 400 V ~ 50 Hz L1 L2 L1 L2 Breaker Breaker Outdoor unit2 Indoor unit Indoor unit (Transmission) (Transmission) Outdoor unit L1 L2 L1 L2 1 2 3 1 2 3...
  • Page 224 ¢ Recommended wiring connection Up to 3 indoor units can be connected to one outdoor unit. Operation of all indoor units is same. The simultaneous multi system is effective for anomalistic floors and wide floors. Connection example Twin connection type Triple connection type Outdoor unit –...
  • Page 225 4-3. Control patterns ¢ 1-Remote controller control This is the most basic system. Wired type or wireless type remote controller can be selected. Wired Wireless remote controller remote controller Outdoor unit – indoor unit connection cable Junction box (Local purchase) Indoor unit –...
  • Page 226 ¢ Remote controller group control 1 or 2-remote controllers can simultaneously control up to 16 indoor units. • Wired remote controller type Outdoor unit – indoor unit Junction box connection cable (Local purchase) Indoor unit – indoor unit Remote controller cable connection cable •...
  • Page 227 ¢ Connection examples • Example 1 (OK) <Triple> Outdoor unit Junction box Refrigerant pipe Indoor unit P: Primary, S: Secondary Remote controller cable Wired remote controller NOTE: Maximum of 2 remote controllers can be connected in the same remote controller group. Also, a remote controller can be connected to any indoor unit.
  • Page 228 • Example 4 (Prohibited) <Twin> Outdoor unit Junction box Refrigerant pipe Indoor unit Wired remote controller NOTE: When connecting more than 2 indoor units in same refrigerant circuit, the remote controller cable must be connected between indoor units. • Example 5 (Prohibited) <Twin>...
  • Page 229 5. System setting 5-1. Indoor unit setting Setting Setting range Setting method Indoor unit Refer to Chapter 8-6. "Function details" on page Set A ◌ “00” or “01” Primary/Secondary 284. (Function number: 51) Refrigerant circuit Refer to Chapter 8-6. "Function details" on page Set B ●...
  • Page 230 ¢ Triple type • Connection example 1 <Triple> <Triple> Outdoor unit Connection cable Junction box Refrigerant pipe Indoor unit SetASetB SetC SetASetB SetC SetASetB SetC (00)(00)(00) (00) (00) Remote controller cable Wired remote controller • Connection example 2 <Triple> <Triple> Outdoor unit Connection cable Junction box...
  • Page 231 ¢ Double twin type • Connection example 1 <Double twin> Outdoor unit Connection cable Junction box Refrigerant pipe Indoor unit SetASetB SetC SetASetB SetC SetASetB SetC SetASetB SetC (00)(00)(00) (00) (00) (00) Remote controller cable Wired remote controller • Connection example 2 <Double twin>...
  • Page 232 ¢ Mixed • Connection example 1 <Twin> <Triple> Outdoor unit Connection cable Junction box Refrigerant pipe Indoor unit SetASetB SetC SetASetB SetC SetASetB SetC SetASetB SetC SetASetB SetC (00) 01 02 01 01 03 01 01 04 (00) (00) (00) (00) Remote controller cable Wired remote controller...
  • Page 233 6. External input and output 6-1. Indoor unit Connector Other than high High static Input Output Remarks static pressure pressure duct duct type type Control CN102 CN114 (Operation/Stop or — For details, refer to Forced stop) external input and CN103 CN115 —...
  • Page 234 ¢ External input • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m. • The wire connection should be separate from the power cable line. ...
  • Page 235 • Circuit diagram example • Contact capacity: DC 24 V or more, 10 mA or more. Indoor unit Connected unit control PCB • *1: PCB of Communication kit is used for wall mounted type . Connector Example: Switch • *2: Make the distance from the PCB to the connected unit within 10 m.
  • Page 236 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Operation status output Indoor unit type Connector Compact cassette Cassette Slim duct CN103 Duct Floor/Ceiling Ceiling CN20 Air conditioner operation status signal can be output.
  • Page 237  Fresh air control output Indoor unit type Connector Compact cassette Cassette Slim duct Duct Floor/Ceiling — Ceiling — Signal linked to air conditioner indoor fan on can be output. * However, signal becomes off during cold air prevention control operation. •...
  • Page 238  Auxiliary heater output Indoor unit type Connector Compact cassette — Cassette — Slim duct CN10 Duct CN10 Floor/Ceiling — Ceiling — Signal is output from connector when indoor fan and compressor turn on under heating operation. *Signal output performance specifications are as shown as follows: Example: When Set Temperature (Ts) is 22 °C •...
  • Page 239 • Circuit diagram example Indoor unit Connected unit control PCB Example: Example: Heater 12 V Connector Relay unit Relay power On/Off supply 10 m* Signal Locally purchased – Relay spec.: Rated DC 12 V, 50 mA to less. – *: Make the distance from the PCB to the connected unit within 10 m. Operation Heating operation...
  • Page 240 6-2. Outdoor unit Connector Input Output Remarks CN131 Low noise mode — CN132 Peak cut mode — For details, refer to external input and output settings. CN136 — Error status CN137 — Compressor status ¢ External input With using external input function, on/off status of “Low noise mode” and “Peak cut mode” can be specified by the external signal.
  • Page 241  Peak cut mode By performing following on-site work, operation that suppresses the current value can be enabled: The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial timer or on/off switch to a connector on the control PCB of the outdoor unit. •...
  • Page 242 ¢ External output With using external output function, some status signals are transmitted to the control PCB, and the related LED lamp indicates the status of this product.  Error status output Signal on air conditioner error status is generated when a malfunction occurs. •...
  • Page 243  Compressor status output Signal on compressor operation status is generated when the compressor is running. • Circuit diagram example (CN137) • 1: Power supply Outdoor unit Voltage (Vcc): DC 24 V or less control PCB Connected unit • 2: Load Connector DC 500 mA or less Power...
  • Page 244 7. Remote controller 7-1. Wireless remote controller (AR-RAH2E/AR-RAH1E) ¢ Overview  AR-RAH2E a FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, and QUIET). b START/STOP button Starts and stops operation. c SET button (vertical) Adjusts the vertical airflow direction. d SET button (horizontal) Adjusts the horizontal airflow direction.
  • Page 245  AR-RAH1E a FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, and QUIET). b START/STOP button Starts and stops operation. c SET button (vertical) Adjusts the vertical airflow direction. d SWING button Sets the automatic swing operation and selects swing mode (Left/right, Stop swing).
  • Page 246 ¢ Specifications  Controller Unit: mm Top view Front view Side view Rear view Size (H × W × D) 170 × 56 × 19 Weight 85 (without batteries) NOTE: Actual number of buttons might be different from the figure above. ...
  • Page 247 7-2. IR receiver kit with Wireless remote controller (UTY- LRHYA2: Optional part) ¢ Overview a FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, and QUIET). b START/STOP button Starts and stops operation. c SET button (vertical) Adjusts the vertical airflow direction. d SET button (horizontal) Adjusts the horizontal airflow direction.
  • Page 248 ¢ Specifications  Controller Unit: mm Top view Front view Side view Rear view Size (H × W × D) 170 × 56 × 19 Weight 85 (without batteries)  Holder Unit: mm Ø 3.5 (hole) 3.5 × 6.5 (hole) Front view Side view Bottom view...
  • Page 249  IR receiver Unit: mm 193.9 31.2 Front view Side view Size (H × W × D) 193.9 × 193.9 × 31.2 Weight - 241 - 7-2. IR receiver kit with Wireless remote controller (UTY-LRHYA2: Optional part) 7. Remote controller...
  • Page 250 7-3. IR receiver kit with Wireless remote controller (UTY- LRHYM: Optional part) ¢ Overview a FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, and QUIET). b START/STOP button Starts and stops operation. c SET button (vertical) Adjusts the vertical airflow direction. d SWING button Sets the automatic swing operation and selects swing mode (Up/down, Left/right, Up/down/left/right, and Stop...
  • Page 251 ¢ Specifications  Controller Unit: mm Top view Front view Side view Rear view Size (H × W × D) 170 × 56 × 19 Weight 85 (without batteries)  Holder Unit: mm Ø 3.5 (hole) 3.5 × 6.5 (hole) Front view Side view Bottom view...
  • Page 252  IR receiver Unit: mm 13.6 57.4 13.6 11.5 18.5 Front view Side view Rear view Size (H × W × D) 145 × 90 × 30 Weight - 244 - 7-3. IR receiver kit with Wireless remote controller (UTY-LRHYM: Optional part) 7.
  • Page 253 7-4. Wired remote controller (UTY-RNNYM) ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
  • Page 254 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 255 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Front view Side view Size (H × W × D) 120 × 120 × 18 Weight Cable length (accessory) Power  Wiring specifications Cable size Wire type Remarks Remote controller cable...
  • Page 256 ¢ Installation  Connection pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit type Connection pattern Compact cassette Cassette Slim duct Pattern A Duct Floor/Ceiling Ceiling Pattern B  Pattern A Connect the end of remote controller cable directly to the exclusive terminal block. M4 screw Remote controller Outdoor unit or Power supply terminal...
  • Page 257 7-5. Wired remote controller (UTY-RVNYM: Optional part) ¢ Overview a Display panel (with backlight) b Screen switch button (Left) c Menu button d Cancel button e Cursor button f Screen switch button (Right) g Power indicator h On/off button i Enter button - 249 - 7-5.
  • Page 258 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 259 ¢ Specifications Unit: mm 21.3 Front view Side view Size (H × W × D) 120 × 120 × 21.3 Weight  Wiring specifications Cable size Wire type Remarks Remote controller cable Polar 3 core Use sheathed PVC cable. 0.33 mm - 251 - 7-5.
  • Page 260 ¢ Installation (Remote control main unit) Installation space: Unit : mm or more or more or more 220 or more* NOTE: Secure enough space where a flat-blade screwdriver to remove the case can be inserted. Installation procedures: 1. Process the remote controller cable. Unit : mm 1.
  • Page 261 3. Attach the remote controller. • When attaching to switch box: a. Seal the wiring hole of the remote controller cable. b. Put a remote controller cable through the hole of the rear case. c. Fix the rear case by securing it with attached screws (2 places). •...
  • Page 262 4. Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the cable tie. Cut off the excess cable tie. Tightening torque Terminal screw 0.8 to 1.2 N•m 1. 12V (Red) 2. Signal (White) 3.
  • Page 263 5. Attach the front case. • Insert after adjusting upper part of front case. • When insert the front case, do not pinch the cable. Front case Click! Good Prohibited Prohibited Prohibited CAUTION Insert the upper case firmly. If improperly attached, it will cause the upper case to fall off. - 255 - 7-5.
  • Page 264 ¢ Installation  Connection pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit type Connection pattern Compact cassette Cassette Slim duct Pattern A Duct Floor/Ceiling Ceiling Pattern B  Pattern A Connect the end of remote controller cable directly to the exclusive terminal block. M4 screw Remote controller Outdoor unit or Power supply terminal...
  • Page 265 7-6. Simple remote controller (UTY-RSNYM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b Display backlight button Lights during operation. c Operation lamp Lights during operation. d FAN button Selects the fan speed (AUTO ,HIGH , MED , and QUIET ).
  • Page 266 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 267 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm hole x 2 hole x 2 Front View Side View Rear View Size (H × W × D) 120 × 75 × 14 Weight Cable length (accessory) Power ...
  • Page 268 ¢ Installation  Connection pattern NOTE: Connection pattern is different according to type of Indoor unit. Indoor unit type Connection pattern Compact cassette Cassette Slim duct Pattern A Duct Floor/Ceiling Ceiling Pattern B  Pattern A Connect the end of remote controller cable directly to the exclusive terminal block. M4 screw Remote controller Outdoor unit or Power supply terminal...
  • Page 269 8. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 8-1. Indoor unit (setting by DIP switch and jumper wire) By using some components on the PCB, you can change the function settings.
  • Page 270 ¢ Dip switch setting Remote controller address setting: When operating a number of indoor units by using a wired remote controller, DIP switch setting for assigning unit number to each indoor unit is required. DIP switches are normally set to make the unit number 00. Remote DIP switch number controller...
  • Page 271 8-2. Indoor unit (setting by wireless remote controller) CAUTION This setting changes the function settings used to control the indoor unit according to the installa- tion conditions. Incorrect settings can cause a product malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 272  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the FAN and the SET TEMP. but- tons, press the RESET button. SET TEMP. ( ) RESET Function setting mode display Press the SET TEMP.
  • Page 273 Proceed to number setting by pressing the FAN button. To return to the function number selection, press the FAN button again. Select the setting number by pressing the or the button. Each time the MODE button is pressed, it switches between the left digit and the right digit. Change digit Send the function mode information by pressing the TIMER MODE button once.
  • Page 274 Exit the function setting mode by pressing the RESET button. RESET To set custom code , , or , perform same procedures for each code.  Setting up each indoor unit Repeat step from 1. to 11. to set up each indoor unit. If the custom code is other than " ", steps from 1.
  • Page 275  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the remote controller dis- play.
  • Page 276 Press the MODE button again to return to the clock display. The custom code will be changed. • If no buttons are pressed within 30 seconds after the custom code is displayed, the system returns to the original clock display. In this case, start again from step 1. •...
  • Page 277 8-3. Indoor unit (setting by wired remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 278 ¢ UTY-RNNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to Function details Remote controller address Setting number Refer to Function details Λ SET TEMP. “V” and “ ”...
  • Page 279 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit. Not good Good ● Data is not set up on the indoor unit Data is correctly set up on the indoor unit correctly (-- is displayed.) (Flashing display changes to illuminated display.) ●...
  • Page 280 ¢ UTY-RVNYM  Function setting procedure Connect the power supply of the outdoor unit. Switch to the function setting mode. When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen. If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor”...
  • Page 281 Select the [Function No.] with pressing the [Cursor button (Left/Right)], and select the Function No. to be set with pressing the [Cursor button (Up/Down)]. Function setting Mo 10:00AM R.C. Function Setting address Cancel: Version Error history Select the [Setting No.] with pressing the [Cursor button (Left/Right)], and select the Setting No. to be set with pressing the [Cursor button (Up/Down)].
  • Page 282 When [Cancel button] is pressed twice while “Function setting” screen is displayed, it switches to the “Submenu” screen. Function setting Mo 10:00AM R.C. Function Setting Submenu Mo 10:00AM address Date and time Screen Cancel: Filter sign Version Error history R.C. sensor control Room temp.
  • Page 283 8-4. Indoor unit (setting by simple remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 284 ¢ UTY-RSNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to Function details Refer to Function details Remote controller address START/STOP button Transmits function setting FAN button SET TEMP.
  • Page 285 Select the setting number by pressing the SET TEMP. or SET TEMP. button. The setting number indicator flashes during setting number selection. Setting number Example) Function number : 30, Setting number : 01 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit.
  • Page 286  Resetting the power after setting up function of all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 287 8-5. Outdoor unit ¢ Local setting switch buttons  Control PCB and switch buttons location Control PCB of the outdoor unit is located as shown in the following figure. LED display and button - 279 - 8-5. Outdoor unit 8. Function settings...
  • Page 288  Switch buttons and the functions LED display part Button part SW107 SW108 SW109 SW112 SW110 LED lamp Function or operation method Lights on while power on. (1) POWER/MODE Green Local setting in outdoor unit or error code is displayed with blink. (2) ERROR Blinks during error operation.
  • Page 289  Function setting table LED display PUMP Factory Setting item LOW NOISE PEAK CUT POWER DOWN setting ERROR MODE (L1) (L2) (L3) (L4) (L5) (L6) Low noise Level 1 ○ ○ ○ ● ○ ○ ● ♦ mode Level 2 ○...
  • Page 290 ¢ Local setting procedure NOTE: Before performing the function setting, be sure to stop the operation of the air conditioner.  Low noise mode Press the MODE switch button (SW107) for 3 seconds or more to switch to “Local setting mode”.
  • Page 291  Peak cut mode Press the MODE switch button (SW107) for 3 seconds or more to switch to “Local setting mode”. After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch but- ton (SW109). PUMP POWER LOW NOISE PEAK CUT DOWN...
  • Page 292 8-6. Function details ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Function Compact Slim...
  • Page 293 1) Remote controller address setting NOTES: • Because this setting is normally done automatically when 2-wire-type wired remote controller is installed, setting is unnecessary. Multiple indoor units can be operated by using one wired remote controller. Set the unit number of each indoor unit. Function number Setting value Setting description...
  • Page 294 3) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting...
  • Page 295 7) Vertical airflow direction range control In a concealed installation, change the setting to "Fixed" (02) to restrict the movement of the upper air outlet so that the airflow is only towards the horizontal direction. To prevent draft, change the setting to "Upward" (01). Note that the airflow in certain usage conditions may leave the ceiling dirty.
  • Page 296 10) Room temperature sensor control for heating Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. Function number Setting value Setting description Factory setting Standard ♦...
  • Page 297 15) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description Factory setting Operation/Stop mode 1 ♦ (Setting prohibited) Forced stop mode Operation/Stop mode 2 16) Room temperature sensor switching (Aux.) To use the temperature sensor on the wired remote controller only, change the setting to "Wired re- mote controller"...
  • Page 298 8-7. Wired remote controller (UTY-RNNYM) Prohibited Dual remote controller setting Prohibited DIP switch 1 °F/°C switch Prohibited Memory backup setting * Do not use DIP switch 2. ¢ Switch location Front case (back side) DIP switch 2 DIP switch 1 ¢...
  • Page 299  SW6: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure. Memory backup Factory setting Disable ♦...
  • Page 300 8-8. Wired remote controller (UTY-RVNYM) Memory backup setting DIP switch 1 Dual remote controller setting ¢ Switch location ¢ DIP switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 301 8-9. Simple remote controller (UTY-RSNYM) Prohibited Dual remote controller setting °F/°C switch DIP switch Prohibited Prohibited Prohibited ¢ Switch location DIP Switch ¢ DIP switch setting  SW2: Dual remote controller setting Set the remote controller SW2 according to the following table. Primary unit Secondary unit Number of remote controller...
  • Page 302 9. Check and test 9-1. Test run ¢ Pre-test run check items Check column Check item Is the outdoor unit securely installed? Have you performed gas leakage inspection? (Connection joints of various pipes (flange connection, brazing)) Is the heat insulation done completely? (Gas pipe, liquid pipe, drain hose extension on indoor unit side etc) Is the water discharging from drain without any problems? Are the cables connected correctly?
  • Page 303 2. Press the ENTER button for more than 3 seconds. PUMP PEAK POWER ERROR DOWN NOISE MODE (L1) (L2) (L3) (L4) (L5) (L6) ○ ○ ○ ○ ○ ○ Blink Blink 3. Press the SELECT button, LED of the test run mode Switched between "COOL " and "HEAT". •...
  • Page 304 9-2. Error code If an error occurs, the LED will light up to display the error location and the error code. ¢ Error display mode Display when an error occurs. PUMP PEAK POWER ERROR DOWN NOISE MODE (L1) (L2) (L3) (L4) (L5) (L6)
  • Page 305 9-3. Pump down WARNING • Never touch electrical components such as the terminal blocks except the button on the display board. It may cause a serious accident such as electric shock. • During the pump-down operation, make sure that the compressor is turned off before you re- move the refrigerant piping.
  • Page 306 5. When LED display changes as shown in the below figure, close the 3-way valve on the gas pipe side tightly. PUMP PEAK POWER ERROR DOWN NOISE MODE (L1) (L2) (L3) (L4) (L5) (L6) ● ○ ● ○ ○ ○ ○...
  • Page 307 10. Optional parts installation 10-1. Drain pump unit for duct type (UTZ-PX1NBA) ¢ Specifications Unit Specifications Height of drain up Maximum 1000 Power source — 220—240 V, 50/60 Hz Power input (230 V, 50/60 Hz) 12/10.8 Current (230 V, 50/60 Hz) 114/92 Dimensions (H ×...
  • Page 308 ¢ Installation place Connected drain pipe (VP25) (I.D.: 25; O.D.: 32) Rear view 470 or more 150 or more Front view Drain pump unit 1,177 1,135 Top view NOTES: • Leave the space required to service the unit. • Set a maintenance hole near the drain pump unit. ¢...
  • Page 309 ¢ Installing hose Example of wrong construction Vertical Downward Upward Bend radius is 60 mm or more Trap Horizontal Downward gradient of 1/50 to 1/100 Part: Hose Vertical loop ¢ Installing pipe Rise Gas of 1.5-2 m Air bleeding Supporter Locally arrangerd pipe VP25...
  • Page 310 10-2. Drain pump unit for ceiling type (UTR-DPB24T) ¢ Applicable indoor units Type Model name Ceiling type ABYG30LRTE, ABYG36LRTE, and ABYG45LRTA ¢ Installing drain pump unit and electrical wiring To indoor unit Drain hose B circuit board Float switch wire Drain pan assy (Connector: Red) Drain pump wire...
  • Page 311 10-3. Fresh air intake kit for cassette type (UTZ-VXRA) ¢ Specifications Model name UTZ-VXRA 2-way intake Fresh air Max. fresh air intake intake volume (For High) 1-way intake Φ 100 Connection duct type 120 × 840 × 840 Dimensions (H × W × D) Gross 165 ×...
  • Page 312 ¢ Airflow 1-way intake 2-way intake Airflow (m³/h) Unit: mm For 2-way intake For 1-way intake 1,000 1,000 Measurement position of shown in the graph Measurement position of shown in the graph - 304 - 10-3. Fresh air intake kit for cassette type (UTZ-VXRA) 10.
  • Page 313 ¢ Fresh air control output • You can control duct fan by synchronization with fan operation of indoor unit. • Wire for fresh air control output is supplied with Fresh air intake kit. • Connection diagram For Relay Output voltage: DC 12 V Permissible current: 15 mA Relay Fuse...
  • Page 314 ¢ Accessories Part name Exterior Q’ty Part name Exterior Q’ty Installation manual Insulation 4 Duct flange Cable tie Extension wire for White Cover 1 set louver Extension wire for Screw receiver kit Wire Hook plate 2 set (External output 1) Wire Shutter plate (External output 2)
  • Page 315 ¢ Installation precautions • About Fresh air intake kit – The Fresh air intake kit can be installed onto cassette type air conditioners. – The volume of ventilated air provided by the Fresh air intake kit may be unable to fulfill ventila- tion regulations in all countries.
  • Page 316 ¢ Installation  Mounting of indoor unit • For mounting, refer to the installation manual provided with indoor unit. • When installing this product to existing indoor units, adjust the installation height of the indoor units to height 260 to 265 mm as shown below. Unit: mm Indoor unit Metal hanging fastener...
  • Page 317  Installation of Fresh air intake kit Attach the Fresh air intake kit to the main body using the bolts provided. DRAIN PIPE Metal fittings DRAIN PIPE Bolt × 4 Attach the Hook plate by each corner of the Fresh air intake kit. (The attaching screws are at- tached to the body of the Fresh air intake kit and must be loosened before installing.) Hook plate Attached...
  • Page 318 Install the duct. a. Fasten the connecting parts of the ducts with bands, and wrap with vinyl tape to ensure no air leaks. (Carry out the work to ensure no air leakage at a pressure of 200 Pa.) NOTE: Do not construct the duct in the manner of below. •...
  • Page 319 3. The existing temperature sensor will not be used so remove it from the sensor holder, and once more install the empty sensor holder (without sensor) in the control box. CAUTION Make sure to install the sensor holder inside the control box, as it is a fire hazard. Otherwise, it may cause fire.
  • Page 320 Install cassette grille panel according to the installation instruction sheet provided. Metal fittings ¢ Installation example • Standard Indoor unit Under the roof Outside Room Panel Outler air Room air Outler air • Case 1: Intake by fan of indoor unit Air filter Connecting duct (locally purchased)
  • Page 321 10-4. Fresh air intake kit for compact cassette type (UTZ-VXAA) ¢ Specifications Model name UTZ-VXAA Fresh air Max. fresh air intake intake volume (For High) Ø 100 Connection duct type 120 × 570 × 570 Dimensions (H × W × D) Gross 165 ×...
  • Page 322 ¢ Airflow Airlfow (m³/h) Unit: mm Measurement position of shown in the graph - 314 - 10-4. Fresh air intake kit for compact cassette type (UTZ-VXAA) 10. Optional parts installation...
  • Page 323 ¢ Fresh air control output • You can control duct fan by synchronization with fan operation of indoor unit. • Wire for fresh air control output is supplied with Fresh air intake kit. • Connection diagram For Relay Output voltage: DC 12 V Permissible current: 15 mA Relay Fuse...
  • Page 324 ¢ Accessories Part name Exterior Q’ty Part name Exterior Q’ty Wire Installation manual (External output 1) Wire Chamber (External output 2) Wire Wire cover (External output 3) Screw Bolt White Extension wire for 1 set Cable tie louver Extension wire for Extension wire for receiver kit receiver kit...
  • Page 325 ¢ Installation precautions • About Fresh air intake kit – The Fresh air intake kit can be installed onto cassette type air conditioners. – The volume of ventilated air provided by the Fresh air intake kit may be unable to fulfill ventila- tion regulations in all countries.
  • Page 326 ¢ Installation  Mounting of indoor unit • For mounting, refer to the installation manual provided with indoor unit. • When installing this product to existing indoor units, adjust the installation height of the indoor units to height 260 to 265 mm as shown below. Unit: mm Indoor unit Metal hanging fastener...
  • Page 327 Install the chamber. Fit the four-sided holes of the chamber together with the hook fittings of the Fresh air intake kit (in two places), and secure the attached chamber in place with screws provided. Ø100 mm Screw × 2 Hook fittings •...
  • Page 328 Install the duct. Fasten the connecting parts of the ducts with band, and wrap with vinyl tape to ensure no air leaks. (Carry out the work to ensure no air leakage at a pressure of 200 Pa.) NOTE: Do not construct the duct in the manner of below. •...
  • Page 329  Installation of Cassette grille Connect extension wire for use with louvers, or extension wire for optical receiver after provi- sional attaching of the decoration panel. Tie the wires together with the fasteners provided and insert into the hole of the Fresh air intake kit.
  • Page 330 10-5. Auto louver grille kit (UTD-GXTB-W) ¢ Specifications Model name UTD-GXTB-W Power supply Connecting with Control box of indoor unit Fixing of Auto louver grille Screw fixing to flange or rectangular duct Extension square duct limit 1.0 m (Max. duct length between indoor unit and grille) Dimensions (H ×...
  • Page 331 ¢ Accessories Part name Exterior Q’ty Part name Exterior Q’ty 10 mm Installation manual Screw A 10 mm Operating manual Screw B Grille Cable clip Bracket frame Cable tie Bushing - 323 - 10-5. Auto louver grille kit (UTD-GXTB-W) 10. Optional parts installation...
  • Page 332 ¢ Installation precautions • Select the installation location that meets the following requirement and that is approved by the customer. – Cool and warm air should reach the entire room. D ≤ 1,000 mm floor NOTE: • *1: For air velocity and air temperature distribution during heating, refer to "Air ve- locity and temperature distributions"...
  • Page 333 Part 4. OPTIONAL PARTS...
  • Page 334 1. Branch pipes 1-1. Model: UTP-SX272A Unit: mm Port diameters Liquid pipe Q’ty Gas pipe Q’ty Ø15.88 Ø9.52 Ø25.40 Ø12.70 Ø22.22 Ø9.52 Ø15.88 Dimensions Liquid pipe Gas pipe Heat insulation cover Liquid pipe Q’ty Gas pipe Q’ty - 326 - 1-1.
  • Page 335 1-2. Model: UTP-SX372A Unit: mm Port diameters Liquid pipe Q’ty Gas pipe Q’ty Ø22.22 Ø12.70 Ø25.40 Ø9.52 Ø15.88 Dimensions Liquid pipe Gas pipe Heat insulation cover Liquid pipe Q’ty Gas pipe Q’ty Others Adapter Q’ty Cable tie Q’ty Ø6.35 Ø9.52 - 327 - 1-2.
  • Page 336 1-3. Model: UTP-SX236A Unit: mm Port diameters Liquid pipe Q’ty Gas pipe Q’ty Ø12.70 Ø6.35 Ø9.52 Ø15.88 Ø6.35 Ø12.70 Ø12.70 Ø19.05 Dimensions Liquid pipe Gas pipe Heat insulation cover Liquid pipe Q’ty Gas pipe Q’ty - 328 - 1-3. Model: UTP-SX236A 1.
  • Page 337 1-4. Model: UTP-SX254A Unit: mm Port diameters Liquid pipe Q’ty Gas pipe Q’ty Ø15.88 Ø9.52 Ø15.88 Ø9.52 Ø9.52 Ø19.05 Ø12.70 Ø15.88 Dimensions Liquid pipe Gas pipe Heat insulation cover Liquid pipe Q’ty Gas pipe Q’ty Others Adapter Q’ty Ø6.35 Ø9.52 - 329 - 1-4.
  • Page 338 2. Controllers 2-1. Lineup Type Wired remote controller Wireless remote controller Indoor unit type AR-RAH1E UTY-RVNYM UTY-RNNYM AR-RAH2E Compact cassette ◌ ◌ ● Cassette ◌ ● ◌ — Slim duct ◌ ● ◌ — Duct ◌ ● ◌ — Floor/Ceiling ◌...
  • Page 339 2-2. Parts Wired remote controller Wireless remote controller UTY-RVNYM UTY-RNNYM AR-RAH1E AR-RAH2E IR receiver kit with Wireless remote controller Simple remote controller UTY-LRHYA2 UTY-LRHYM UTY-RSNYM - 331 - 2-2. Parts 2. Controllers...
  • Page 340 3. Cassette grille 3-1. Lineup Indoor units Type Model Cassette Compact cassette UTG-UGYA-W ◌ — Cassette grille UTG-UFYD-W — ◌ ◌: Optional, —: Not applicable 3-2. Parts Cassette grille UTG-UGYA-W UTG-UFYD-W - 332 - 3-1. Lineup 3. Cassette grille...
  • Page 341 4. Others 4-1. Lineup Indoor unit Outdoor Type Model Compact Floor/ unit Cassette Slim duct Duct Ceiling cassette Ceiling UTR-YDZB ◌ — — — — — — Air outlet shutter plate UTR-YDZK — ◌ — — — — — Insulation kit UTZ-KXGC ◌...
  • Page 342 4-2. Parts Air outlet shutter plate Air outlet shutter plate Model: UTR-YDZB Model: UTR-YDZK For compact cassette type For cassette type Insulation kit for high humidity Insulation kit for high humidity Model: UTZ-KXGC Model: UTZ-KXRA Insulation Insulation For compact cassette type For cassette type Fresh air intake kit Fresh air intake kit...
  • Page 343 Long-life filter Auto louver grille kit Model: UTD-LF25NA Model: UTD-GXTB-W For slim duct type For duct type Remote sensor unit Drain pomp unit Model: UTY-XSZX Model: UTZ-PX1NBA For slim duct type and duct type For duct type Drain pump unit External control set Model: UTR-DPB24T Model: UTD-ECS5A...