System Configuration - Fujitsu AUYG07LVLA Design & Technical Manual

Hide thumbs Also See for AUYG07LVLA:
Table of Contents

Advertisement

EXAMPLE 2
Outdoor unit
Separation
tube
Branch box
Indoor unit

System configuration

1
Model name
AS18
Capacity class (kW)
5.0
Rated capacity of
5.27
cooling (kW)
Capacity ratio
(Total capacity of indoor units) / (Capacity of outdoor unit)
= (16.11) / (14.0) = 115.1% (Within 80% to 130%)
Selection of separation tube
Model
UTP-SX248A
Selection of branch box
Model
UTP-PY03A (3 branches)
UTP-PY02A (2 branches)
Selection of pipe size
Liquid pipe size
mm (in.)
Gas pipe size
mm (in.)
Pipe length
m
Liquid pipe size
mm (in.)
Gas pipe size
mm (in.)
Pipe length
m
a
d
f
g
h
1
2
3
(5.0kW)
(2.0kW)
(2.0kW)
Indoor unit
Indoor unit
(Indoor units)
2
3
AS07
AS07
2.0
2.0
2.05
2.05
Q'ty
1
Q'ty
2
None
a
b
c
9.52
9.52
(3/8)
(3/8)
15.88
15.88
(5/8)
(5/8)
7
25
h
i
j
6.35
6.35
6.35
(1/4)
(1/4)
(1/4)
9.52
9.52
9.52
(3/8)
(3/8)
(3/8)
5
5
5
c
Branch box
i
j
4
5
(2.5kW)
(2.0kW)
Indoor unit
Indoor unit
Indoor unit
4
5
6
AS09
AS07
AS07
2.5
2.0
2.0
2.64
2.05
2.05
d
e
9.52
(3/8)
15.88
12.70
(5/8)
10
k
l
6.35
(1/4)
9.52
(3/8)
5
- (06 - 21) -
k
6
(2.0kW)
7
8
f
g
6.35
6.35
(1/4)
(1/4)
9.52
(1/2)
(3/8)
5
5
m
6. SYSTEM DESIGN
Total
capacity
(kW)
16.11