[Installation precautions]
When inside
the ceiling
is high
temperature
and high
humidity
Moist air curve
Relative humidity 80%
Dry bulb temperature 30°C (86°F)
Fig.A
When using
an external
duct
When the
remote
controller
installation site
is bad
Contents
When the indoor unit is installed where the
inside of the ceiling is 30°C (86°F) RH80%
or greater, the dew point temperature of the
outer perimeter may become higher than the
cabinet surface temperature and moisture will
condense on the surface of the cabinet and
water drops may fall inside the room.
e er to ig.
In addition, the humidity may vary
considerably the same as when the inside of
the ceiling is close to hermetically sealed and
used as the outside air intake path.
Condition which
requires addition of
outside heat insulation
Covered gas pipe
(heat insulation
strengthened)
Contents
When using an external duct to take in new
fresh air, etc., condensation may form on
the surface of the duct due to the effect of
the outside air temperature and the humidity
inside the ceiling.
If the cold or warm air blown out from the air
conditioner directly contacts the thermostat
section of the remote controller, the outlet
temperature of the air conditioner may be
sensed and room temperature control will be
different from the room temperature and "not
cooled" or "not heated" or other trouble may
occur.
In addition, there is the possbility that the
same kind of trouble may also occur when the
remote controller is effected by direct sunlight.
- (06 - 152) -
Countermeasures (Reference)
1) Add heat insulating material
to the outside of the indoor
unit cabinet.
*Regarding the cassette type,
use of the "high humidity
correspondence kit (option)"
is recommended.
2) Strengthen the heat
insulating material of the
refrigerant piping and drain
piping also
3) When the humidity inside
the ceiling changes
considerably, install a
ventilation port
Work method when reinforcing the heat insulation
of on-site piping
Slit of heat insulating
material facing upward
Flare connection
Heat insulating material
Small exposed part of
(procured at the site)
copper pipe is desirable.
Fig.B
Countermeasures (Reference)
1) Always perform heat
insulation processing.
(Heat insulating material:
Glass wool 25mm (31/32 in.)
thick or more.)
1) Install the remote controller
where it will not be directly
exposed to the cold or hot
air.
2) Install the remote controller
where it will not be directly
exposed to sunlight or
strong lighting.
e er to ig.
Heat insulation
reinforcement material
(procured at the site)
To indoor unit
Fit tightly (purpose is
Binding material
to cover the sealant)
6. SYSTEM DESIGN