Piping Design; Important Items When Using Refrigerant R410A - Fujitsu AUYG07LVLA Design & Technical Manual

Hide thumbs Also See for AUYG07LVLA:
Table of Contents

Advertisement

2.

PIPING DESIGN

2-1.

IMPORTANT ITEMS WHEN USING REFRIGERANT R410A

R410A operates at higher pressure and has less solubility with mineral oil than
traditional R22 refrigerant. Therefore, the lubricant and a part of pipe material are different.
Some special tools are necessary.
REFRIGERANT PIPING MATERIAL AND WALL THICKNESS
It is necessary to use seamless copper tubes for refrigerant use.
Thickness of tubes are shown in table below.
Endurance pressure of the pipe must be 4.2 MPa.
Nominal Diameter
(in)
Outside Diameter
(mm)
Material
Wall Thickness *2
(mm)
owab e tensi e stress
*2: Endurance pressure of the pipe must be 4.2 MPa.
Please select the pipe size in accordance with local rules.
LUBRICANT
Refrigerant
R410A (Mixed refrigerant)
Lubricant
TOOLS
R410A work requires a number of special tools. Since the tools (marked *4 below) for R22
work cannot be used for R410A, prepare them beforehand.
Tool name
Pipe cutter
Flaring tool *4
Torque wrench *4
Expander
Pipe bender
Nitrogen gas
Welder
Gauge manifold *4
Charging hose *4
Vacuum pump (with adaptor) *4
Electronic scale for refrigerant charging
Gas leak tester *4
*4: Please refer to the service manual for details.
1/4"
3/8"
1/2"
6.35
9.52
12.70
JIS H3300 C1220T-O or equivalent *1
0.8
0.8
0.8
2
)
Synthetic oil
Pipe cutting
Pipe aring wor
Flare nut connection
Expansion at pipe connection
Pipe bending work
Pipe interior oxidation prevention
Pipe brazing
Vacuum evacuation and refrigerant
charging Operation check
Gas leakage test
- (06 - 11) -
5/8"
3/4"
15.88
19.05
1.0
1.2
Process and application
Refrigerant piping work
Air tightness test
Air tightness test ~
Refrigerant additional charging
Vacuum drying
Refrigerant additional charging
6. SYSTEM DESIGN

Hide quick links:

Advertisement

Table of Contents
loading