Fujitsu AUYG07LVLA Design & Technical Manual page 270

Hide thumbs Also See for AUYG07LVLA:
Table of Contents

Advertisement

Limitation check
Total pipe length
Between outdoor unit and the farthest indoor unit
Between outdoor unit and branch boxes
Between branch box and indoor unit
etween outdoor unit and the first separation tube
Calculation of additional charge refrigerant
Liquid pipe size
mm (in.)
Additional refrigerant
g/m
Liquid pipe length
m
Additional charge = (21 x 30) + (58 x 42) = 3066 g = 3.07 kg
Diagram
Total
a + c + k
a + c + d
Total
f + g + h + i + j + k
Each unit
f, g, h, i, j, k
a
6.35
9.52
(1/4)
(3/8)
21
58
30
42
- (06 - 22) -
Example
Limitation
m
m
72
115 or less
37
70 or less
42
55 or less
30
60 or less
5
Between 3 to 15
7
5 or more
6. SYSTEM DESIGN
Judge
OK
OK
OK
OK
OK
OK

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents