Password Security Menu - GE B90 Instruction Manual

Ur series low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

8.1 PASSWORD SECURITY
A command or setting write operation is required to update the state of all the remote and local security operands
shown above. Changing the password, or any other setting, does not take the relay out of service. The relay is
taken out of service when a settings file is written to it.
NOTE
PATH: SETTINGS
PRODUCT SETUP
 SECURITY
PATH: SETTINGS
PRODUCT SETUP
 CHANGE LOCAL
 PASSWORDS
Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters.
When a
CHANGE COMMAND PASSWORD
interface, the following message sequence is invoked:
1.
ENTER NEW PASSWORD: ____________.
2.
VERIFY NEW PASSWORD: ____________.
3.
NEW PASSWORD HAS BEEN STORED.
8
To gain write access to a "Restricted" setting, program the
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the "Restricted" level according
to the access level timeout setting values.
If an entered password is lost (or forgotten), consult the factory with the corresponding
If the setting and command passwords are identical, then this one password allows access to both commands and
settings.
NOTE
If a remote connection is established, local passcodes are not visible.
NOTE
8-2
SECURITY
ACCESS LEVEL:
Restricted
 CHANGE LOCAL
MESSAGE
 PASSWORDS
 ACCESS
MESSAGE
 SUPERVISION
 DUAL PERMISSION
MESSAGE
 SECURITY ACCESS
PASSWORD ACCESS
MESSAGE
EVENTS: Disabled

SECURITY
CHANGE LOCAL PASSWORDS
CHANGE COMMAND
PASSWORD: No
CHANGE SETTING
MESSAGE
PASSWORD: No
ENCRYPTED COMMAND
MESSAGE
PASSWORD: ----------
ENCRYPTED SETTING
MESSAGE
PASSWORD: ----------
or
CHANGE SETTING PASSWORD
B90 Low Impedance Bus Differential System

8.1.2 PASSWORD SECURITY MENU

Range: Restricted, Command, Setting,
Factory Service (for factory use only)
see page 8–2
see page 8–4
see page 8–4
Range: Disabled, Enabled
Range: No, Yes
Range: No, Yes
Range: 0 to 9999999999
Note: ---------- indicates no password
Range: 0 to 9999999999
Note: ---------- indicates no password
setting is programmed to "Yes" via the front panel
setting in the main security menu to "Setting" and
ACCESS LEVEL
ENCRYPTED PASSWORD
8 SECURITY
8.1.3 LOCAL PASSWORDS
.