7.2 TARGETS
Description of problem: One or more GOOSE devices are not responding.
How often the test is performed: Event driven. The test is performed when a device programmed to receive GOOSE
messages stops receiving. This can be from 1 to 60 seconds, depending on GOOSE packets.
What to do: Check GOOSE setup.
TEMP MONITOR:
OVER TEMPERATURE
Latched target message: Yes.
Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C).
How often the test is performed: Every hour.
What to do: Remove the B90 from service and install in a location that meets operating temperature standards.
UNEXPECTED RESTART:
Press "RESET" key
Latched target message: Yes.
Description of problem: Abnormal restart from modules being removed or inserted while the B90 is powered-up, when
there is an abnormal DC supply, or as a result of internal relay failure.
How often the test is performed: Event driven.
What to do: Contact the factory.