Chapter 17 - Cyber-Security
4.2.2

PASSWORD RULES

Default passwords are blank for Level 1 and are AAAA for Levels 2 and 3
Passwords may be any length between 0 and 8 characters long
Passwords may or may not be NERC compliant
Passwords may contain any ASCII character in the range ASCII code 33 (21 Hex) to ASCII code 122 (7A Hex)
inclusive
Only one password is required for all the IED interfaces
4.2.3

ACCESS LEVEL DDBS

In addition to having the 'Access level' cell in the 'System data' column (address 00D0), the current level of access
for each interface is also available for use in the Programming Scheme Logic (PSL) by mapping to these Digital
Data Bus (DDB) signals:
HMI Access Lvl 1
HMI Access Lvl 2
HMI Access Lvl 3
FPort AccessLvl1
FPort AccessLvl2
FPort AccessLvl3
RPrt1 AccessLvl1
RPrt1 AccessLvl2
RPrt1 AccessLvl3
RPrt2 AccessLvl1
RPrt2 AccessLvl2
RPrt2 AccessLvl3
Key:
HMI = Human Machine Interface
FPort = Front Port
RPrt = Rear Port
Lvl = Level
4.3

ENHANCED PASSWORD SECURITY

Cyber-security requires strong passwords and validation for NERC compliance.
4.3.1

PASSWORD STRENGTHENING

NERC compliant passwords have the following requirements:
At least one upper-case alpha character
At least one lower-case alpha character
At least one numeric character
At least one special character (%,$...)
At least six characters long
374