GE B90 Instruction Manual page 183

Ur series low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

5 SETTINGS
b) FLEXCURVE™ CONFIGURATION WITH ENERVISTA UR SETUP
The EnerVista UR Setup software allows for easy configuration and management of FlexCurves™ and their associated
data points. Prospective FlexCurves™ can be configured from a selection of standard curves to provide the best approxi-
mate fit, then specific data points can be edited afterwards. Alternately, curve data can be imported from a specified file
(.csv format) by selecting the Import Data From EnerVista UR Setup setting.
Curves and data can be exported, viewed, and cleared by clicking the appropriate buttons. FlexCurves™ are customized
by editing the operating time (ms) values at pre-defined per-unit current multiples. Note that the pickup multiples start at
zero (implying the "reset time"), operating time below pickup, and operating time above pickup.
c) RECLOSER CURVE EDITING
Recloser curve selection is special in that recloser curves can be shaped into a composite curve with a minimum response
time and a fixed time above a specified pickup multiples. There are 41 recloser curve types supported. These definite oper-
ating times are useful to coordinate operating times, typically at higher currents and where upstream and downstream pro-
tective devices have different operating characteristics. The recloser curve configuration window shown below appears
when the Initialize From EnerVista UR Setup setting is set to "Recloser Curve" and the Initialize FlexCurve button is
clicked.
The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set-
tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio.
NOTE
GE Multilin
Multiplier: Scales (multiplies) the curve operating times
Addr: Adds the time specified in this field (in ms) to each
Minimum Response Time (MRT): If enabled, the MRT setting
defines the shortest operating time even if the curve suggests
a shorter time at higher current multiples. A composite operating
characteristic is effectively defined. For current multiples lower
than the intersection point, the curve dictates the operating time;
otherwise, the MRT does. An information message appears
when attempting to apply an MRT shorter than the minimum
curve time.
High Current Time:
from which point onwards the operating time is fixed. This is
normally only required at higher current levels. The
defines the high current pickup multiple; the
operating time.
Figure 5–16: RECLOSER CURVE INITIALIZATION
B90 Low Impedance Bus Differential System
operating time value.
Allows the user to set a pickup multiple
5.3 SYSTEM SETUP
5
HCT Ratio
HCT
defines the
842721A1.CDR
5-63

Advertisement

Table of Contents
loading

This manual is also suitable for:

B90 ur series

Table of Contents