1 GETTING STARTED
5.
Enter an IP address with the first three numbers the same as the IP address of the B90 relay and the last number
different (in this example, 1.1.1.2).
6.
Enter a subnet mask equal to the one set in the B90 (in this example, 255.0.0.0).
7.
Click OK to save the values.
Before continuing, it will be necessary to test the Ethernet connection.
1.
Open a Windows console window by selecting Start > Run from the Windows Start menu and typing "cmd".
2.
Type the following command:
C:\WINNT>ping 1.1.1.1
3.
If the connection is successful, the system will return four replies as follows:
Pinging 1.1.1.1 with 32 bytes of data:
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
4.
Note that the values for
time
If the following sequence of messages appears when entering the
Pinging 1.1.1.1 with 32 bytes of data:
Request timed out.
Request timed out.
Request timed out.
Request timed out.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the physical connection between the B90 and the laptop computer, and double-check the programmed IP address in
the

PRODUCT SETUP
COMMUNICATIONS
If the following sequence of messages appears when entering the
Pinging 1.1.1.1 with 32 bytes of data:
Hardware error.
Hardware error.
Hardware error.
Hardware error.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the physical connection between the B90 and the laptop computer, and double-check the programmed IP address in
the

PRODUCT SETUP
COMMUNICATIONS
If the following sequence of messages appears when entering the
GE Multilin
and
will vary depending on local network configuration.
TTL

NETWORK
IP ADDRESS

NETWORK
IP ADDRESS
B90 Low Impedance Bus Differential System
1.3 ENERVISTA UR SETUP SOFTWARE
command:
C:\WINNT>ping 1.1.1.1
setting, then repeat step 2 in the above procedure.
command:
C:\WINNT>ping 1.1.1.1
setting, then repeat step 2 in the above procedure.
command:
C:\WINNT>ping 1.1.1.1
1
1-13