Breaker Failure - GE B90 Instruction Manual

Ur series low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

5 SETTINGS

PATH: SETTINGS
GROUPED ELEMENTS
 BREAKER FAILURE
 BREAKER FAILURE
 CURRENT SUPV 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
 BREAKER FAILURE 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
SETTING GROUP 1(6)
BF1 CURRENT SUPV
FUNCTION: Disabled
BF1 CT:
F1
BF1 AMP SUPV
PICKUP: 1.050 pu
BF1 AMP HISET
PICKUP: 1.050 pu
BF1 AMP LOSET
PICKUP: 1.050 pu
BF1 FUNCTION:
Disabled
BF1 INITIATE:
Off
BF1 USE AMP SUPV:
Yes
BF1 USE SEAL-IN:
Yes
BF1 AMP SUPV OP A:
Off
BF1 AMP SUPV OP B:
Off
BF1 AMP SUPV OP C:
Off
BF1 USE TIMER 1:
Yes
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 2:
Yes
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 3:
Yes
B90 Low Impedance Bus Differential System
5.5 GROUPED ELEMENTS


BREAKER FAILURE 1(24)

Range: Disabled, Enabled
Range: Available current channels
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: Yes, No
Range: Yes, No
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
5.5.4 BREAKER FAILURE
5-89
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

B90 ur series

Table of Contents