APPENDIX C
Header.
Substation.
Communication.
IED section (one or more).
DataTypeTemplates.
The root file structure of an SCD file is illustrated below.
Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to
signals.
The Substation node describes the substation parameters:
GE Multilin
C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
SCL
Header (id, version, revision, toolID, nameStructure)
Substation
Communication
IED Section (IED 1)
IED Section (IED 2)
Other IED Sections
DataTypeTemplates
Figure C–6: SCD FILE STRUCTURE, SCL (ROOT) NODE
Substation
EquipmentContainer
VoltageLevel
Function
842792A1.CDR
Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE
B90 Low Impedance Bus Differential System
842791A1.CDR
PowerSystemResource
Power Transformer
GeneralEquipment
EquipmentContainer
Bay
Voltage
PowerSystemResource
SubFunction
GeneralEquipment
C