Communications - GE B90 Instruction Manual

Ur series low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 COMMUNICATIONS
5
b) SERIAL PORTS
PATH: SETTINGS
PRODUCT SETUP
 SERIAL PORTS
The B90 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for
local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet
or RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that
these parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any of
these ports may be connected to a computer running EnerVista UR Setup. This software can download and upload setting
files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and con-
nected to a DCS, PLC or PC using the RS485 ports.
5-12


COMMUNICATIONS

 SERIAL PORTS
 NETWORK
MESSAGE
 MODBUS PROTOCOL
MESSAGE
 DNP PROTOCOL
MESSAGE
 DNP / IEC104
MESSAGE
 POINT LISTS
 IEC 61850 PROTOCOL
MESSAGE
 WEB SERVER
MESSAGE
 HTTP PROTOCOL
 TFTP PROTOCOL
MESSAGE
 IEC 60870-5-104
MESSAGE
 PROTOCOL
 SNTP PROTOCOL
MESSAGE

COMMUNICATIONS
RS485 COM1 BAUD
RATE: 19200
RS485 COM1 PARITY:
MESSAGE
None
RS485 COM1 RESPONSE
MESSAGE
MIN TIME:
RS485 COM2 BAUD
MESSAGE
RATE: 19200
RS485 COM2 PARITY:
MESSAGE
None
RS485 COM2 RESPONSE
MESSAGE
MIN TIME:
B90 Low Impedance Bus Differential System
See below.
See page 5–13.
See page 5–13.
See page 5–14.
See page 5–17.
See page 5–19.
See page 5–30.
See page 5–31.
See page 5–31.
See page 5–32.
SERIAL PORTS
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Only
active if CPU Type E is ordered.
Range: None, Odd, Even
Only active if CPU Type E is ordered
Range: 0 to 1000 ms in steps of 10
Only active if CPU Type E is ordered
0 ms
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10
0 ms
5 SETTINGS
5.2.5 COMMUNICATIONS
GE Multilin