B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 8 of 44)
ADDR
REGISTER NAME
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
40E3
IEC 60870-5-104 Protocol Cyclic Data Transmit Period
40E4
IEC 60870-5-104 Current Default Threshold
40E6
IEC 60870-5-104 Voltage Default Threshold
40E8
IEC 60870-5-104 Power Default Threshold
B
40EA
IEC 60870-5-104 Energy Default Threshold
40EC
IEC 60870-5-104 Power Default Threshold
40EE
IEC 60870-5-104 Other Default Threshold
40F0
IEC 60870-5-104 Client Address (5 items)
4104
IEC 60870-5-104 Redundancy Port Enabled/Disabled
4105
IEC Communications Reserved (57 items)
413E
High Enet Traffic Function
413F
High Enet Traffic Events
4140
DNP Object 1 Default Variation
4141
DNP Object 2 Default Variation
4142
DNP Object 20 Default Variation
4143
DNP Object 21 Default Variation
4144
DNP Object 22 Default Variation
4145
DNP Object 23 Default Variation
4146
DNP Object 30 Default Variation
4147
DNP Object 32 Default Variation
Ethernet Switch (Read/Write Setting)
4148
Ethernet Switch IP Address
414A
Ethernet Switch Modbus IP Port Number
414B
Ethernet Switch Port 1 Events
414C
Ethernet Switch Port 2 Events
414D
Ethernet Switch Port 3 Events
414E
Ethernet Switch Port 4 Events
414F
Ethernet Switch Port 5 Events
4150
Ethernet Switch Port 6 Events
Ethernet Switch (Read Only Actual Values)
4151
Ethernet Switch MAC Address
4154
Ethernet Switch Port 1 Status
4155
Ethernet Switch Port 2 Status
4156
Ethernet Switch Port 3 Status
4157
Ethernet Switch Port 4 Status
4158
Ethernet Switch Port 5 Status
4159
Ethernet Switch Port 6 Status
415A
Switch Firmware Version
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) Function
4169
Simple Network Time Protocol (SNTP) Server IP Address
416B
Simple Network Time Protocol (SNTP) UDP Port Number
Clock (Read/Write Command)
41A0
Real Time Clock Set Time
Clock (Read/Write Setting)
41A2
SR Date Format
41A4
SR Time Format
41A6
IRIG-B Signal Type
41A7
Clock Events Enable / Disable
41A8
Time Zone Offset from UTC
41A9
Daylight Savings Time (DST) Function
41AA
Daylight Savings Time (DST) Start Month
41AB
Daylight Savings Time (DST) Start Day
B-16
RANGE
0 to 65535
1 to 65535
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
0 to 4294967295
0 to 1
0 to 1
0 to 1
0 to 1
1 to 2
1 to 3
0 to 3
0 to 3
0 to 3
0 to 3
1 to 5
0 to 5
0 to 4294967295
1 to 65535
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
---
0 to 2
0 to 2
0 to 2
0 to 2
0 to 2
0 to 2
0.00 to 99.99
0 to 1
0 to 4294967295
1 to 65535
0 to 235959
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
–24 to 24
0 to 1
0 to 11
0 to 6
B90 Low Impedance Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
s
1
F001
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F126
---
1
F001
---
1
F102
---
1
F102
---
1
F001
---
1
F001
---
1
F523
---
1
F524
---
1
F523
---
1
F523
---
1
F001
---
1
F525
---
1
F003
---
1
F001
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
---
F072
---
1
F134
---
1
F134
---
1
F134
---
1
F134
---
1
F134
---
1
F134
---
0.01
F001
---
1
F102
---
1
F003
---
1
F001
---
1
F050
---
1
F051
---
1
F052
---
1
F114
---
1
F102
hours
0.5
F002
---
1
F102
---
1
F237
---
1
F238
DEFAULT
0
60
30000
30000
30000
30000
30000
30000
0
0 (No)
0
0 (Disabled)
0 (Disabled)
2
2
0 (1)
0 (1)
0 (1)
0 (1)
1
0 (1)
3232235778
502
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (Disabled)
0
0 (Fail)
0 (Fail)
0 (Fail)
0 (Fail)
0 (Fail)
0 (Fail)
0
0 (Disabled)
0
123
0
0
0
0 (None)
0 (Disabled)
0
0 (Disabled)
0 (January)
0 (Sunday)