B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 16 of 44)
ADDR
REGISTER NAME
6F9E
Terminal Voltage 1 Secondary
6F9F
...Repeated for Terminal Voltage 2
6FA2
...Repeated for Terminal Voltage 3
6FA5
...Repeated for Terminal Voltage 4
6FA8
...Repeated for Terminal Voltage 5
B
6FAB
...Repeated for Terminal Voltage 6
6FAE
...Repeated for Terminal Voltage 7
6FB1
...Repeated for Terminal Voltage 8
6FB4
...Repeated for Terminal Voltage 9
6FB7
...Repeated for Terminal Voltage 10
6FBA
...Repeated for Terminal Voltage 11
6FBD
...Repeated for Terminal Voltage 12
B90 Function (Read/Write Setting)
6FC0
B90 Function
Terminal Frequency (Read Only)
6FD0
Terminal Frequency
6FD1
Terminal Tracking Frequency
Breaker Failure Current Supervision (Read/Write Grouped Setting) (24 modules)
7000
Breaker Failure 1 Current Supervision Function
7001
Breaker Failure 1 Current Supervision CT
7002
Breaker Failure 1 Current Supervision Amp Supv Pickup
7003
Breaker Failure 1 Current Supervision Amp Hiset Pickup
7004
Breaker Failure 1 Current Supervision Amp Loset Pickup
7005
Reserved (4 items)
7009
...Repeated for Breaker Failure 2
7014
...Repeated for Breaker Failure 3
701B
...Repeated for Breaker Failure 4
7024
...Repeated for Breaker Failure 5
702D
...Repeated for Breaker Failure 6
7036
...Repeated for Breaker Failure 7
703F
...Repeated for Breaker Failure 8
7048
...Repeated for Breaker Failure 9
7051
...Repeated for Breaker Failure 10
705A
...Repeated for Breaker Failure 11
7063
...Repeated for Breaker Failure 12
706C
...Repeated for Breaker Failure 13
7075
...Repeated for Breaker Failure 14
707E
...Repeated for Breaker Failure 15
7087
...Repeated for Breaker Failure 16
7090
...Repeated for Breaker Failure 17
7099
...Repeated for Breaker Failure 18
70A2
...Repeated for Breaker Failure 19
70AB
...Repeated for Breaker Failure 20
70B4
...Repeated for Breaker Failure 21
70BD
...Repeated for Breaker Failure 22
70C6
...Repeated for Breaker Failure 23
70CF
...Repeated for Breaker Failure 24
Breaker Failure (Read/Write Grouped Setting) (24 modules)
7100
Breaker Failure 1 Function
7101
Breaker Failure 1 Initiate
7102
Breaker Failure 1 Use Amp Supervision
7103
Breaker Failure 1 Use Seal In
7104
Breaker Failure 1 Amp Supervision OpA
7105
Breaker Failure 1 Amp Supervision OpB
B-24
RANGE
50 to 240
0 to 1
2 to 90
2 to 90
0 to 1
0 to 23
0.001 to 30
0.001 to 30
0.001 to 30
0 to 65535
0 to 1
0 to 65535
0 to 1
0 to 1
0 to 65535
0 to 65535
B90 Low Impedance Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
V
0.1
F001
---
1
F250
Hz
0.01
F001
Hz
0.01
F001
---
1
F102
---
1
F400
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
---
1
F001
---
1
F102
---
1
F300
---
1
F126
---
1
F126
---
1
F300
---
1
F300
DEFAULT
664
0 (Logic)
0
0
0 (Disabled)
0
1050
1050
1050
0
0 (Disabled)
0
1 (Yes)
1 (Yes)
0
0
GE Multilin