5.2 PRODUCT SETUP
This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1.
Configure the transmission dataset by making the following changes in the
IEC 61850 PROTOCOL

GOOSE 1
CONFIG GSE 1 DATASET ITEMS
Set
to "GGIO1.ST.Ind1.q" to indicate quality flags for GGIO1 status indication 1.
ITEM 1
Set
to "GGIO1.ST.Ind1.stVal" to indicate the status value for GGIO1 status indication 1.
ITEM 2
Set
to "MMXU1.MX.Hz.mag.f" to indicate the analog frequency magnitude for MMXU1 (the metered fre-
ITEM 3
quency for SRC1).
The transmission dataset now contains a quality flag, a single point status Boolean value, and a floating point analog
value. The reception dataset on the receiving device must exactly match this structure.
2.
Configure the GOOSE service settings by making the following changes in the

IEC 61850 PROTOCOL
settings menu:
RABLE GOOSE 1
Set
CONFIG GSE 1 FUNCTION
Set
CONFIG GSE 1 ID
Set
CONFIG GSE 1 DST MAC
Set the
CONFIG GSE 1 VLAN PRIORITY
Set the
CONFIG GSE 1 VLAN ID
5
Set the
CONFIG GSE 1 ETYPE APPID
the configuration on the receiver (the default value is "0").
Set the
CONFIG GSE 1 CONFREV
this example it can be left at its default value.
3.
Configure the data by making the following changes in the
COL
GGIO1 STATUS CONFIGURATION
Set
GGIO1 INDICATION 1
a contact input, virtual input, a protection element status, etc.).
4.
Configure the MMXU1 Hz Deadband by making the following changes in the
IEC 61850 PROTOCOL
Set
MMXU1 HZ DEADBAND
change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency.
The B90 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
1.
Configure the reception dataset by making the following changes in the
61850 PROTOCOL

1
CONFIG GSE 1 DATASET ITEMS
Set
to "GGIO3.ST.Ind1.q" to indicate quality flags for GGIO3 status indication 1.
ITEM 1
Set
to "GGIO3.ST.Ind1.stVal" to indicate the status value for GGIO3 status indication 1.
ITEM 2
Set
to "GGIO3.MX.AnIn1.mag.f" to indicate the analog magnitude for GGIO3 analog input 1.
ITEM 3
The reception dataset now contains a quality flag, a single point status Boolean value, and a floating point analog
value. This matches the transmission dataset configuration above.
2.
Configure the GOOSE service settings by making the following changes in the

REMOTE DEVICE 1
Set
REMOTE DEVICE 1 ID
5-24
GSSE/GOOSE CONFIGURATION
settings menu:
GSSE/GOOSE CONFIGURATION
to "Enabled".
to an appropriate descriptive string (the default value is "GOOSEOut_1").
to a multicast address (for example, 01 00 00 12 34 56).
; the default value of "4" is OK for this example.
value; the default value is "0", but some switches may require this value to be "1".
value. This setting represents the ETHERTYPE application ID and must match
value. This value changes automatically as described in IEC 61850 part 7-2. For
settings menu:
to a FlexLogic™ operand used to provide the status of GGIO1.ST.Ind1.stVal (for example,


MMXU DEADBANDS
MMXU1 DEADBANDS
to "0.050%". This will result in an update to the MMXU1.MX.mag.f analog value with a
GSSE/GOOSE CONFIGURATION
settings menu:
settings menu:
to match the GOOSE ID string for the transmitting device. Enter "GOOSEOut_1".
B90 Low Impedance Bus Differential System
PRODUCT SETUP

TRANSMISSION
CONFIGURABLE GOOSE

TRANSMISSION

PRODUCT SETUP
PRODUCT SETUP
settings menu:
PRODUCT SETUP


RECEPTION
CONFIGURABLE GOOSE
5 SETTINGS

COMMUNICATION
CONFIGURABLE

PRODUCT SETUP
COMMUNICATION
CONFIGURABLE GOOSE
CONFIGU-

COMMUNICATION
IEC 61850 PROTO-

COMMUNICATION

COMMUNICATION
CONFIGURABLE GOOSE

INPUTS/OUTPUTS
REMOTE DEVICES