GE B90 Instruction Manual page 335

Ur series low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 3 of 44)
ADDR
REGISTER NAME
Element Targets (Read/Write)
14C2
Target to Read
Element Targets (Read Only)
14C3
Target Message
Contact Input/Output States (Read Only)
1500
Contact Input States (6 items)
1508
Virtual Input States (8 items)
1510
Contact Output States (4 items)
1518
Contact Output Current States (4 items)
1520
Contact Output Voltage States (4 items)
1528
Virtual Output States (6 items)
1530
Contact Output Detectors (4 items)
Remote Input/Output States (Read Only)
1540
Remote Device States (2 items)
1542
Remote Input States (4 items)
1550
Remote Devices Online
1551
Remote Double-Point Status Input 1 State
1552
Remote Double-Point Status Input 2 State
1553
Remote Double-Point Status Input 3 State
1554
Remote Double-Point Status Input 4 State
1555
Remote Double-Point Status Input 5 State
Platform Direct Input/Output States (Read Only)
15C0
Direct Input States (6 items)
15C8
Direct Outputs Average Message Return Time 1
15C9
Direct Outputs Average Message Return Time 2
15CA
Direct Inputs/Outputs Unreturned Message Count - Ch. 1
15CB
Direct Inputs/Outputs Unreturned Message Count - Ch. 2
15D0
Direct Device States
15D1
Reserved
15D2
Direct Inputs/Outputs CRC Fail Count 1
15D3
Direct Inputs/Outputs CRC Fail Count 2
Ethernet Fibre Channel Status (Read Only)
1610
Ethernet Primary Fibre Channel Status
1611
Ethernet Secondary Fibre Channel Status
Bus Actuals (Read Only) (4 modules)
21D0
Bus Zone 1 Differential Magnitude
21D4
Bus Zone 1 Differential Angle
21D5
Bus Zone 1 Restraint Magnitude
21D7
Bus Zone 1 Restraint Angle
21D8
Bus Zone 1 Maximum CT
21DA
Reserved (4 items)
21DE
...Repeated for Bus Zone 2
21EC
...Repeated for Bus Zone 3
21FA
...Repeated for Bus Zone 4
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 modules)
2620
Remote Double-Point Status Input 1 Device
2621
Remote Double-Point Status Input 1 Item
2622
Remote Double-Point Status Input 1 Name
2628
Remote Double-Point Status Input 1 Events
2629
... Repeated for Double-Point Status Input 2
2632
... Repeated for Double-Point Status Input 3
263B
... Repeated for Double-Point Status Input 4
GE Multilin
RANGE
0 to 65535
---
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 3
0 to 3
0 to 3
0 to 3
0 to 3
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 2
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 50000
---
0 to 1
1 to 32
0 to 64
1 to 64
0 to 1
B90 Low Impedance Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F001
---
---
F200
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F500
---
1
F126
---
1
F605
---
1
F605
---
1
F605
---
1
F605
---
1
F605
---
1
F500
ms
1
F001
ms
1
F001
---
1
F001
---
1
F001
---
1
F500
---
1
F001
---
1
F001
---
1
F001
---
1
F134
---
1
F134
A
0.001
F060
degrees
0.1
F002
A
0.001
F060
degrees
0.1
F002
---
1
F060
---
---
F001
---
1
F126
---
1
F001
---
1
F606
---
1
F205
---
1
F102
DEFAULT
0
"."
B
0
0
0
0
0
0
0
0
0
0 (No)
3 (Bad)
3 (Bad)
3 (Bad)
3 (Bad)
3 (Bad)
0
0
0
0
0
0
0
0
0
0 (Fail)
0 (Fail)
0
0
0
0
1
0
0 (No)
1
0 (None)
"RemDPS Ip 1"
0 (Disabled)
B-11

Advertisement

Table of Contents
loading

This manual is also suitable for:

B90 ur series