Notifier AFP-300 Installation Manual page 77

Analog fire panel
Hide thumbs Also See for AFP-300:
Table of Contents

Advertisement

Wiring a Signaling Line Circuit (SLC)
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
www.PDF-Zoo.com
6/&3HUIRUPDQFH
SLC performance depends on the type of circuit: Style 4, Style 6, or Style 7. Table 2-17
lists the trouble conditions that result when a fault exists on an SLC.
Fault in Loop
Style 4
Open
Trouble
Ground
Alarm/Trouble
Short
Trouble
Short and open
Trouble
Short and ground
Trouble
Open and ground
Trouble
Communications loss
Trouble
Trouble indicates a trouble signal will be generated at the control panel during the
abnormal condition.
Alarm/Trouble indicates an alarm signal can be transmitted to the control panel during
the abnormal condition.
SLC operation meeting Style 7 requirements isolates entire physical zones on the SLC
from faults that occur within other areas of the SLC.
Style 6
Alarm/Trouble
Alarm /Trouble
Trouble
Trouble
Trouble
Alarm /Trouble
Trouble
Table 2-17 SLC Performance
 ,QVWDOODWLRQ
Style 7
Alarm/Trouble
Alarm/Trouble
Alarm/Trouble
Trouble
Alarm/Trouble
Alarm/Trouble
Trouble
2-41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp-400

Table of Contents