Remote printers require a 120 VAC, 50/60 Hz primary power source and a secondary
power source (battery backup). Because a secondary power source is not provided, use
a separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective
Signaling. Install the remote printer to the control panel as follows:
1.
Make a custom cable for connecting the printer EIA-232 port to CPU TB1 (Printer)
using the wiring specifications shown in Figure 2-49:
PRN (EIA-232)
TX (Pin 3)
RX (Pin 2)
REF (Pin 7)
)LJXUH  351 WR &38 &DEOH :LULQJ 6SHFLILFDWLRQV
2.
Connect the cable between the CPU and the PRN-4 through an EIA-232 interface
as shown in Figure 2-50:
3OXJ WKH '% FRQQHFWRU LQWR WKH
(,$ SRUW RI WKH SULQWHU351
351
&38
)LJXUH  5HPRWH 3ULQWHU &RQQHFWLRQV