Notifier AFP-300 Installation Manual page 157

Analog fire panel
Hide thumbs Also See for AFP-300:
Table of Contents

Advertisement

Releasing Applications
2YHUYLHZ
7\SLFDO &RQQHFWLRQV
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
www.PDF-Zoo.com
&RQQHFWLQJD5HOHDVLQJ'HYLFHWRWKH036
When connecting a releasing device to an MPS-400, note the following:
1.
The control panel provides four NAC/Releasing Circuits (Style Y or Z). Each
circuit can provide 2.5 A. Total current drawn from the MPS-400 cannot exceed
6 A (see Table G-2 on page G-3). Use UL-listed 24 VDC appliances only.
2.
Circuits are supervised and power-limited. For more information, refer to the
Notifier Compatibility Document.
3.
For NFPA 13 and 15 applications, disable the Soak Timer (Soak=0000); for
NFPA 16 applications, set the Soak Timer (0600-0900 seconds). Refer to the
AFP-300/AFP-400 Programming Manual for instructions on setting the Soak
Timer.
4.
In applications not requiring power-limited circuits – a) End-of-Line devices
(PN REL-2.2K) are not required; however, the releasing device circuit is not
supervised against shorts; b) Limited energy cable cannot be used for wiring of a
releasing device circuit; c) Maintain a 0.25 inch spacing between the releasing
circuit device wiring and any power-limited circuit wiring; and d) Program the
releasing circuit for type code RELEASE CKT.
Figure 5-18 shows typical connections for wiring a releasing device to an MPS-400:
)LJXUH  7\SLFDO &RQQHFWLRQ RI D 5HOHDVLQJ 'HYLFH WR WKH 036
 $SSOLFDWLRQV
5(/.
%URZQ
5HG
7%²7% ² 1$&5HOHDVLQJ
  1$&5HOHDVLQJ RXWSXW VRXUFH
 ² 1$&5HOHDVLQJ RXWSXW VRXUFH
  &ODVV $ UHWXUQ
 ² &ODVV $ UHWXUQ
(DFK FLUFXLW LV SRZHUOLPLWHG DQG
VXSHUYLVHG
3URJUDP UHOHDVLQJ FLUFXLWV ZLWK W\SH
FRGH 5(/ &.7 8/&

²
5-19