To connect the UZC-256 to the CPU, follow these steps:
1.
Connect the main power harness (PN 75100, provided with the UZC-256) from
MPS-400 connector J1 to UZC-256 connector P2.
2.
Connect the EIA-485 ACS annunciator port as follows:
CPU, TB4-1 to UZC-256 TB2-3
CPU, TB4-2 to UZC-256 TB2-5
(UZC-256 terminals are numbered from right to left.)
3.
Connect notification appliance power devices as shown in Figure 5-15.
:LULQJ'LDJUDP
Figure 5-15 shows typical connections between the UZC-256 and NACs: