AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
www.PDF-Zoo.com
$SSHQGL['&57&RQILJXUDWLRQ
2YHUYLHZ
The CRT-2 communicates with the control panel through a protocol defined by thirteen
groups of parameters. To access a parameter group, press the corresponding function
key (F1-F13) as shown in Table D-1. You can then program parameters in each group.
6HWWLQJ&573DUDPHWHUV
Enter the CRT-2 setup menu by pressing and holding the <Ctrl> key while pressing the
<Scroll Lock> key. Use arrow keys to move through the selections in each setup group;
press the space bar to view the options for each parameter. When finished
programming all setup groups, press the <Pause> key. To save all changes, press <Y>.
Function
CRT-2 Parameters
Key
F1: Quick
Emulation=CRT-2
Comm Mode=Full Duplex
Enhanced=On
F2:Genrl
Emulation=CRT-2
Auto Font Load=On
Monitor Mode=Off
Host/Printer=EIA/Aux
F3: Displ
Page Length=24
Display Cursor=On
Columns=80
Scroll=Jump
F4: Kybd
Language=U.S.
Keyclick=Off
Key Lock=Caps
F5: Keys
Enter Key=<CR>
Alt Key=Meta
Pound Key=U.S.
F6: Ports
EIA Baud Rate=2400
Aux Baud Rate=2400
EIA Xmt=Xon-Xoff
Aux Xmt=Xon-Xoff
EIA Break=Off
Aux Break=Off
F7: Host
Comm Mode=Full Duplex
Recv <DEL>=Ignore
Send Block Term=<CR>
F8: Print
Prnt Line Term=<CR><LF>
F9: Emul
Attribute=Page
WPRT Intensity=Dim
WPRT Blink=Off
Status Line=Off
F10
Setup Group F10 does not affect communications with the control panel.
F11
Setup Group F11 does not affect communications with the control panel.
F12: Prog
Program the function keys as follows:
F1 ~A F2 ~B F3 ~C F4 ~D F5 ~E F6 ~F F7 ~G F8 ~H F9 ~I F10 ~J F11 ~K F12 ~L F13 ~M
F14 ~N F15 ~O F16 ~P Shift F13 ~Q
7DEOH ' &57 )XQFWLRQ .H\V DQG 3DUDPHWHUV
EIA Baud Rate=2400
EIA Data Format=8/1/N
Aux Baud Rate=2400
Aux Data Format=7/1/E
Language=U.S.
Host/Printer=EIA/Aux
Enhanced=On
Auto Wrap=Off
Auto Page=Off
Auto Scroll=On
Bell Volume=09
Warning Bell=On
Screen Length=26 Lines
Screen Video=Normal
Cursor=Blink Line
Auto Adjust Cursor=On
Width Change Clear=Off
Speed=Normal
Refresh Rate=60 Hz
Overscan Borders=Off
Char Set Mode=ASCII
Key Mode=ASCII
Key Repeat=Off
Margin Bell=Off
Keyboard Present=Yes
Return Key=<CR>
Backspace=<BS>/<DEL>
Disconnect=Pause
Desk Acc=Disabled
EIA Data Format=8/1/N
EIA Parity Check=On
Aux Data Format=7/1/E
Aux Parity Check=On
EIA Recv=Xon-Xoff(XPC)
EIA Xmt Pace=Baud
Aux Recv=Xon-Xoff(XPC)
Aux Xmt Pace=Baud
EIA Modem Control=Off
EIA Disconnect=2 sec
Aux Modem Control=Off
Aux Disconnect=2 sec
Local=Off
Recv <CR>=<CR>
Send ACK=On
Send Line Term=<CR><LF>
Null Suppress=On
Prnt Block Term=<CR>
Secondary Recv=Off
Bright Video=Off
Page Edit=Off
WPRT Reverse=Off
WPRT Underline=Off
Display NV Labels=Off
Save Labels=On
Fkey Speed=Normal
D-1