Field-Wiring the Modules
2YHUYLHZ
1RWH )RU PRUH LQIRUPDWLRQ
UHIHU WR $SSHQGL[ )  8/
3RZHUOLPLWHG :LULQJ
5HTXLUHPHQWV
$50 7HUPLQDO
$VVLJQPHQWV
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
www.PDF-Zoo.com
)LHOG:LULQJWKH$X[LOLDU\5HOD\0RGXOH $50 
This section provides terminal assignments for ARM-4 module control relays K1-K4,
which control nonpower-limited circuits. Wiring requirements follow:
Power-limited and nonpower-limited circuit wiring must remain separated in the
cabinet.
All power-limited circuit wiring must remain at least 0.25 in. away from any
nonpower-limited circuit wiring.
All power-limited and nonpower-limited circuit wiring must enter and exit the
cabinet though different knockouts, conduits, or both.
Table 2-11 contains contact ratings for relays K1-K4 on the ARM-4 module:
Resistive Load
125 VAC
30 VDC
Table 2-11 Contact Ratings for K1-K4 on the ARM-4 Module
Figure 2-43 shows terminal assignments for control relays on the ARM-4 module:
1&
12 &
.
.
1& 12 &
)LJXUH  $50 0RGXOH 7HUPLQDO $VVLJQPHQWV
N.O.
20 A
20 A
1& 12 &
.
1R &RQQHFWLRQ
.
1& 12 &
 ,QVWDOODWLRQ
Contacts
N.C.
10 A
10 A
2-31