Field-Wiring the Modules
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
www.PDF-Zoo.com
)LHOG:LULQJDQ,&0DQGDQ,&(1)3$6W\OH<DQG=
Guidelines for field-wiring include the following:
•
Notification Appliance Circuits (NACs) are supervised, power-limited, and can
connect to an energy-limited cable.
•
Use only the compatible, UL-listed notification appliances listed in the Device
Compatibility Document.
•
Wire notification appliances according to the manufacturer's instructions.
•
Maximum current per circuit is 3.0 A. Maximum current per module depends on
the type of power supply (MPS-400 or AVPS-24).
•
Canadian installations require model N-ELR End-of-Line Resistor Assembly
(Style Y only).
•
Size NAC wiring so the voltage drop does not exceed the minimum rated voltage of
the notification appliance used as the last device on the circuit.
•
For zone coded applications, refer to the UZC-256 manual.
•
The ICM-4 is California Code programmable (microprocessor Rev. B or higher).
To program for California Code, cut diode D35.
7\SLFDO 1)3$ 6W\OH < 1$&
. ZDWW
(/5 31
8/OLVWHG 9'&
3RODUL]HG %HOOV
8/OLVWHG 9'&
3RODUL]HG +RUQV
% $ $¤ %¤ % $ $¤ %¤
)LJXUH )LHOG:LULQJ DQ ,&0
Positions E, F, G, and H are active only with the ICE-4 installed. You can also install a
CRE-4 module on the ICM-4, connected as shown in Figure 2-36:
,&( PRGXOH
,&0 PRGXOH
)LJXUH )LHOG:LULQJ DQ ,&(
7\SLFDO 1)3$ 6W\OH = 1$&
-XPSHUV IRU
XQXVHG
FLUFXLWV
% $ $¤ %¤ % $ $¤ %¤
,QVWDOODWLRQ
-XPSHUV IRU
XQXVHG
FLUFXLWV
/IS]OXK
2-27