&RQQHFWLQJD5HOHDVLQJ'HYLFHWRDQ,&0,&(0RGXOH
When connecting a releasing device to an ICM-4 or ICE-4 module, note the following:
1.
The ICM-4 and ICE-4 provide four NAC/Releasing Circuits (Style Y or Z). Each
circuit can provide 3 A of current. Make sure to keep total system current within
the limits of the power supply. Use UL-listed 24 VDC appliances only.
2.
Circuits are supervised and power-limited. For more information, refer to the
Notifier Compatibility Document.
3.
For NFPA 13 and 15 applications, disable the Soak Timer (Soak=0000); for
NFPA 16 applications, set the Soak Timer (0600-0900 seconds). Refer to the
AFP-300/AFP-400 Programming Manual for instructions on setting the Soak
Timer.
4.
In applications not requiring power-limited circuits – a) End-of-Line devices (PN
REL-4.7K) are not required; however, the releasing device circuit is not supervised
against shorts; b) Limited energy cable cannot be used for wiring of a releasing
device circuit; c) Maintain a 0.25 inch spacing between the releasing circuit device
wiring and any power-limited circuit wiring; and d) Program the releasing circuit
for type code RELEASE CKT.
Figure 5-19 shows typical connections for wiring a releasing device to an ICM-4 or
ICE-4 module:
)LJXUH  7\SLFDO &RQQHFWLRQ RI 5HOHDVLQJ 'HYLFH WR DQ ,&0,&( 0RGXOH
Releasing Applications
5(/.
5HG
(DFK FLUFXLW LV SRZHUOLPLWHG
DQG VXSHUYLVHG
3URJUDP PRGXOHV IRU W\SH
FRGH 5(/ &.7 8/&
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97